EasyManua.ls Logo

Weidmüller UHZ/AR - Page 23

Default Icon
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
23
NAMUR
sensor
UHZ/AR
3+ 1 2 4
NAMUR sensors.
NPN type
3-wire sensor
(O/C outputs)
Sig
UHZ/AR
2+ 5
Power (+ve)
Signal
Power (–ve)
41
3-wire sensors with NPN open collector outputs
PNP type
3-wire sensor
(O/C outputs)
Sig
UHZ/AR
21+ 3
Power (+ve)
Signal
Power (–ve)
4 5
3-wire sensors with PNP open collector outputs
Voltage pulse
source
UHZ/AR
5- 4+ 6
Use terminal 6
for voltages
above 45 V DC
Voltage pulse signals.
Volt-free
contacts
UHZ/AR
ba31 2 4
Volt-free contacts (Max. Freq. 10Hz)
Sensor
UHZ/AR
2 1 Sig4 3
Externally powered NPN open collector sensors
Sensor
UHZ/AR
4 +1 Sig2 3
Externally powered PNP open collector sensors
Input type
Low voltage inputs High voltage inputs
Description
Trigger Reset Trigger Reset
LOAC
HIAC
LOdC
HIdC
CoN
SGL1
SGL2
SGL3
SGL4
50 mV -50 mV 200 mV -400 mV Low level AC signals
2.5 V -2.5 V 14 V -10 V High level AC signals
3.5 V 0.5 V 20 V -2 V Low level DC signals
6 V 3 V 35 V 10 V High level DC signals
6 V 3 V 35 V 10 V Contact closure
200 mV -2.5 V 400 mV -21 V Special signal type
11.5 V 0.5 V 5 V 2.5 V Special signal type
22.0 V 1.0 V 7 V 5 V Special signal type
33.5 V 2.5 V 15 V 10 V Special signal type 4
Input Types