Installation and Startup Guide
This document covers the installation of MT8106iP Series HMI, for the detailed specifications and
operation, please refer to Datasheet, Brochure and EasyBuilder Pro User Manual. Please read all
warnings, precautions, and instructions on the device carefully before use.
Install Environment:
NEMA Rating
The HMI product is NEMA 4 rated (indoor use only).
Electrical
Environment
The HMI product has been tested to conform to European CE requirements. This
means that the circuitry is designed to resist the effects of electrical noise. This
does not guarantee noise immunity in severe cases. Proper wire routing and
grounding will insure proper operation.
Environmental
Considerations
(1) Make sure that the displays are installed correctly and that the operating
limits are followed. Avoid installing units in environments where severe
mechanical vibration or shocks are present.
(2) Do not operate the unit in areas subject to explosion hazards due to
flammable gases, vapors or dusts.
(3) Do not install the unit where acid gas, such as SO2 exists.
(4) This device should be mounted in the vertical position and for use on the flat
surface enclosure.
(5) For use in Pollution Degree 2 Environment and dry location.
(6) Relative Humidity: 10% ~ 90% (non-condensing)
Cleaning
Considerations
Clean the device using dry cloths. Do not use liquid or spray detergents for
cleaning.
IP Rating
IP 65
Warning
Protection impairment if used in a manner not specified by the manufacturer.
ficit de protection si utilisé d'une manière non spécifiée par le fabricant.
Unpacking the Unit
Unpack and check the delivery. If damage is found, please contact the supplier.
NOTE: Place the operator panel on a stable surface during installation. Dropping it or letting it
fall may cause damage.
The package includes:
(1) Installation Instruction, 2-sided A4 *1 (2) Human Machine Interface *1 (3) Power Connector *1
(4) Brackets & Screws *1 pack
Installation Instructions
Use a control box that provides enough stiffness. Cutout
Dimension: 260 mm x 202 mm. Secure the operator panel in
position, using all the fastening holes and the provided
brackets and screws. Screw Torque: 2.6 ~ 3.9 lbf.in. (For
reaching waterproof effect and preventing the panel from
being deformed.)
Plan for adequate space around the unit and inside the
enclosure, for ventilation and cables. Consider the heat from
other devices inside the enclosure. The ambient temperature
around the unit must be 0 ~ 55°C
Minimum required clearances (along the overlay): Top 15 mm / Bottom 50 mm / Sides 15 mm
Maximum panel thickness: 4.5 mm
Power Connections
Power Connector Specifications:
Wire AWG: 24~12
Wiring Conductor Minimum Temperature: 75°C
Screw Torque: 4.5 lbf-in (max.)
Copper conduct only.
Spécifications du connecteur d'alimentation:
AWG de fil: 24 ~ 12
Température minimale du conducteur de câblage: 75°C
Couple de vis: 4.5 lbf-in (max.)
Conducteur en cuivre seulement
NOTE:
1. Connect positive DC line to the ‘+’ terminal and the DC ground
to the ‘- terminal.
2. When downloading project using a USB cable, do not connect
HMI with PLC and PC simultaneously, for electric potential
difference may result in damage to HMI or PC.
System Settings
When HMI is powered up and displays image, click the system setting
button. (Default System Password: 111111)
Go to Security tab, the default password is 111111, click
the buttons to set your own passwords.
In MISC2 tab, if Enable [Reset HMI to default] button in
calibration mode is selected, the [RESET HMI TO
DEFAULT] button can be found in calibration mode, as
shown in Part 8.
Go to the Network tab, you may
choose to auto get DHCP IP, or
designate your own IP. It is necessary
to connect the HMI to your network
through a RJ-45 cable.
EasyBuilder Pro Software Settings
Launch EasyBuilder Pro software, select your project file, press F7 shortcut key to open the download
dialog box: Select Ethernet > IP tab > Enter your HMI IP > Click Download to download this project
file to HMI.
Using screensaver and backlight saver is recommended in order to avoid image persistence caused
by displaying the same image on HMI for a long time.
( Please refer to EasyBuilder Pro User Manual for software operation details. )
5
4
3
6
MT8106iP series
Installation Instruction
Question and Answer IconNeed help?

Do you have a question about the weintek MT8106iP Series and is the answer not in the manual?

weintek MT8106iP Series Specifications

General IconGeneral
Display TypeTFT LCD
Contrast Ratio500:1
BacklightLED
EnclosurePlastic
Touch ScreenResistive
Communication PortsUSB, RS-232, RS-485
Ethernet10/100 Mbps
Power Supply24 V DC
Operating Temperature0°C to 50°C
Storage Temperature-20°C to 60°C
Relative Humidity10% to 90% (non-condensing)
Protection RatingIP65

Summary

Installation and Startup Guide

Install Environment

Details environment requirements for HMI installation and operation.

Electrical

Specifies electrical considerations for HMI installation.

Environment Considerations

Lists environmental factors to consider for HMI operation.

Cleaning Considerations

Provides guidelines for cleaning the HMI device.

IP Rating

Specifies the Ingress Protection rating of the HMI.

Warning

Important safety warning regarding protection impairment.

Unpacking the Unit

Package Contents

Lists items included in the HMI package.

Installation Instructions

Mounting and Clearances

Guidelines for mounting the HMI and required clearances.

Power Connections

Power Connector Specifications

Details specifications for the HMI power connector.

Power Connection Notes

Crucial notes on connecting power and USB during downloads.

System Settings

System Settings Access

How to access and navigate system settings on the HMI.

Security and Reset Options

Setting passwords and enabling factory reset function.

EasyBuilder Pro Software Settings

Project Download via Ethernet

Steps to download projects using EasyBuilder Pro via Ethernet.

Communication Connections

Communication Ports

Details available communication ports and wiring configurations.

RS232/RS485 Pinouts

Pinout diagrams for COM1, COM2, and COM3 ports.

Touchscreen Calibration Mode

Calibrating the Touchscreen

Procedure to enter and perform touchscreen calibration.

Battery Replacement

Battery Specifications and Handling

Details on battery type, replacement, and handling safety.

DANGER

Hardware Considerations

System designer awareness of device failure risks and safety.

Programming Considerations

Implementing safety checks in controller programs for HMI systems.

Limited Warranty

Product Warranty Terms

Explains the limited warranty coverage and exclusions.