Installation and Startup Guide
This document covers the installation of
TK6070iQ
Series HMI, for the detailed specifications and
operation, please refer to Datasheet and EasyBuilder
8000
User Manual.
Install Environment:
NEMA Rating
TK6070iQ
Series
HMI is NEMA
4
rated.
Electrical
Environment
The
TK6070iQ
Series has been tested to conform to European CE requirements.
This means that the circuitry is designed to resist the effects of electrical noise.
This does not guarantee noise immunity in severe cases. Proper wire routing and
grounding will insure proper operation.
Environmental
Considerations
(1) Make sure that the displays are installed correctly and that the operating
limits are followed. Avoid installing units in environments where severe
mechanical vibration or shocks are present.
(2) Do not operate the unit in areas subject to explosion hazards due to
flammable gases, vapors or dusts.
(3) Do not install the unit where acid gas, such as SO2 exists.
(4) This device should be mounted in the vertical position and for use on the flat
surface enclosure.
(5) Conform to UL508 (ISBN 0-7629-0404-6) machine safety for use in
Pollution Degree 2 Environment.
Unpacking the Unit
Unpack and check the delivery. If damage is found,
notify the supplier.
Installation Instructions
Secure the operator panel in position, using all the fastening holes and the provided brackets
and screws:
Type
A(mm)
B(mm)
TK6070iQ
192
138
Power Connections
System Settings
When HMI powered up and displays image,
click the system setting button.
(Default System Password: 111111)
TK6070iQ
series
Installation Instruction
1
2
NOTE:
Place the operator panel on a stable
surface during installation. Dropping it or
letting it fall may cause damage.
Go to the Security tab, the default
password is 111111, click the button to
set your own password.
NOTE:
1. Connect positive DC line to the ‘+’ terminal
and the DC ground to the- terminal.
2. Please do not connect HMI with PLC and PC
simultaneously to prevent potential difference
from destroying USB ports of HMI and PC.
To make a connection, strip about 3/8” of
insulation off the end of the wire, turn the
connector screw counterclockwise until the gap
is wide open, insert the wire all the way in, and
turn the screw clockwise until it’s tight.
(A)
(B)
Cutout
(1) Installation Instruction, 2-sided A4 *1
(2) Human Machine Interface *1
(3) Power Connector *1
(4) Brackets & Screws V2.1 *1 pack
(1)
(2)
(4)
(3)
Question and Answer IconNeed help?

Do you have a question about the weinview TK6070iQ series and is the answer not in the manual?

weinview TK6070iQ series Specifications

General IconGeneral
Brandweinview
ModelTK6070iQ series
CategoryTouch Panel
LanguageEnglish

Summary

Installation and Startup Guide

Install Environment and Electrical Considerations

Details NEMA rating, CE requirements, electrical noise, and environmental limits for proper operation.

Unpacking the Unit

Check for Damage and Contents

Unpack and inspect the delivery for damage, noting included parts like manuals and brackets.

Installation Instructions

Mounting the Operator Panel

Secure the operator panel using fastening holes, brackets, and screws as per cutout dimensions.

Power Connections

Connecting DC Power

Connect positive DC line to '+' and DC ground to '-' terminals, avoiding simultaneous PLC/PC USB connections.

System Settings

Accessing and Securing System Settings

Access system settings via the display image and set a new password from the default.

EasyBuilder 8000 Software Settings

Software Configuration and Download

Launch EasyBuilder 8000, select project file, and use USB cable for downloading to HMI.

Calibration Mode

Touch Panel Calibration

Select USB cable in Project Manager and click Calibrate Touch Panel to start calibration.

Communication Connections

Pinouts and Cable Requirements

Details pin assignments for RS232/RS485 and recommends cable length and type for reliability.

Safety and Operational Precautions

Power and Electrical Safety

Covers DC power requirements, voltage ranges, fuse protection, isolation, and wiring practices.

Emergency Stop and Wiring

Mandates hard-wired EMERGENCY STOP, proper wire routing, surge suppression, and separation of power/signal wires.

Hardware and Programming Considerations

System Design Safety

Discusses controller failure risks, electrical interference, and implementing limit checks for safety.

Limited Warranty

Warranty Terms and Exclusions

Outlines warranty period, conditions for repair/replacement, and exclusions for misuse or unauthorized service.