POWERPATH
1
2
3
4
ON
OUT1-4
IN>OUT SYNC
WHEELOCK SYNC
TEMPORAL
INPUT SELECT
OUT4
OUT2
OUT3
+
-
-
+
OUT1
-
+
+
IN1
-
TO NEXT APPLIANCE
OR EOLR
RET1
+
-
F
C
P
A
OR RETURN
TO FACP
(CLASS "A")
-
+
1
2
3
4
ON
SW9
POWERPATH
1
2
3
4
ON
OUT1-4
IN>OUT SYNC
WHEELOCK SYNC
TEMPORAL
INPUT SELECT
OR EOLR
(2.2K OHMS)
TO NEXT APPLIANCE
OR EOLR
+
-
IN1
RET1
-
+
OUT1
+
-
A
P
C
F
TO NEXT APPLIANCE
OR EOLR
(2.2K OHMS)
TO NEXT APPLIANCE
OUT2
-
+
TO NEXT APPLIANCE
OR EOLR
(2.2K OHMS)
+
-
OUT3
OR EOLR
(2.2K OHMS)
TO NEXT APPLIANCE
OUT4
-
+
1
2
3
4
ON
SW9
Normal Mode (Class B)
Normal Mode (Class A)
POWERPATH™ Operating Modes (refer to Installation Manual):
Normal Mode: Provides constant 12 VDC or 24 VDC output upon initiation by a
voltage to input IN1 or IN2 or by a contact opening on DRY1 or DRY2. The unit returns
to standby mode when the input is deactivated.
Wheelock Sync Mode: Provides signals for synchronization of patented Wheelock
audible and strobe notification appliances. Audibles can also be silenced in this mode
while the strobes continue to flash.
In>Out Sync Mode: Accepts a coded signal or synchronization signal on the input to
provide a coded output or synchronized output. This signal may come from a FACP,
another POWERPATH or a Wheelock SM or DSM synchronization module. Caution:
Do not use strobes on coded output circuits.
Temporal Mode: Codes the output voltage in a code-3 temporal pattern to drive audible
appliances such as horns, bells or chimes. Caution: Do not use strobes on coded
output circuits.