What to do if the Overload LED is on in my Whistler Group XP1200i?
- CCatherine ThomasJul 27, 2025
The Overload LED on your Whistler Group Inverter might be on due to several reasons: * Your equipment might have a high start-up surge. Try turning the inverter power switch OFF (O) and then ON (l) again until the inverter powers your appliance. Repeat as necessary to get your appliance started. * The battery voltage may be below 10 volts. In this case, recharge or replace the battery. * The equipment being operated draws too much power. Consider using a higher capacity inverter. * The inverter might be too hot (thermal shutdown mode). Allow the inverter to cool, check for adequate ventilation, and reduce the load on the inverter to the rated continuous power output.