EasyManua.ls Logo

Willhi WH7016E - High Temperature Alarm; High Temperature Alarm Settings; Low Temperature Alarm Function; Low Temperature Alarm Settings

Willhi WH7016E
6 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
with "" or "" key adjusted to the screen, appearing "HS" or "LS" code,
press the "SET" key to display the upper or lower limit set value, Then press
"" or "" key to adjust the parameters. HS means upper limit. LS means
lower limit.
For example: the upper and lower limits are used to limit the range of control
temperature that can be set, such as: LS is 10, HS 20, then press the SET key
to adjust the temperature control, it can only be varied between 10 and 20.
High temperature alarm:
If the measured temperature> set temperature + AH alarm output relay. Thermostat alarm
will sound, the display alternately shows H and the current temperature. Alarm, press any
key to stop the alarm and relay output.
High temperature alarm settings:
Press "SET" button and hold more than 3 seconds to enter the menu display, with "" or
"" button transferred to the screen appears "AH" code, press the "SET" key to display
the high-temperature alarm settings, press " "or" "key to adjust the parameters
Low temperature alarm function:
If the measured temperature "set temperature-AL when the alarm output relay.
Thermostat alarm will sound, the display alternately shows L and the current temperature.
Alarm, press any key to stop the alarm and relay output.
low temperature alarm settings:
Press "SET" button and hold more than 3 seconds to enter the menu display, with "" or
"" button transferred to the screen appears "AL" code, press the "SET" key to display
the low temperature alarm settings, press " "or" "key to adjust the parameters
Menu code selection:
Symbol Details Setting
range
Factory
settings
Units
HC
Heating /
cooling
H/C C
D
Hysteresis
0.115
1.0
LS
The minimum
set limit
-9.999.9
-9.9
HS
The maximum
set limit
-9.999.9
99.9
CA
Temperature
calibration
-5.0+5.0
0.0
PT
Delay time
010
1
Minutes
AH
High temperature
alarm
015
1.0
AL low temperature
alarm settings
015
1.0
fault tips:
1)When the sensor disconnected, the screen displays --- and close the
heating wire
2)When the sensor detects the temperature is below -9.9 degrees, the screen
displays LLL
3)When the sensor detects a temperature higher than 99.9 degrees, the
screen displays HHH
Caution for using:
Cooling, heating load must not exceed the output contact capacity, or it
may result in machine damage and cause a fire.
PDF 文件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn

Related product manuals