Quick Start Guide
Before
Installation
• Local device password is 0800.
• In order to access the device on the Web Portal the device needs to be
communicating with our host server.
• A 30 minute timer starts on the device as soon as power is applied. At
least one (1) sensor must be programmed locally or remotely within the
30 minutes or an alarm will occur. This timer is in place to remind install-
ers the device requires programmed sensors for functionality; it can be
canceled by pressing “timer” (F3 button).
• Wired sensor inputs are numbered 1 - 4. Wireless sensors are in posi-
tions 5-12.
• Wirel
ess output relays are assignable and numbered 1 - 8.
• Wireless sensors must be set up locally at the device to ensure com-
munication.
Device Input Voltage 1 1 to 26VDC @ ≤ 500mA current draw
Wireless Sensor Input Voltage
(EA-WMFS, EA-WTS, EA-WHS)
12VDC @ ≤ 100mA current draw via 2.1
mm barrel plug, center positive OR 2 AA
Alkaline Batteries (1.5V Cell)
Device Auxiliary
Output Voltage
Equivalent to DC Input Voltage used: 11 to
26VDC. (Maximum output current 0.5A).
Device and Wireless Sensor
Environmental Operating Range
Temperature: 0°C to 50°C (32°F to 122°F).
Not for installation inside coolers or freez-
ers. Humidity: 5% to 95% RH, non-
condensing.
Ambient Environmental Quality Indoor use intended, non-corrosive environ-
ment.
Relay Contact Ratings Max 30VDC @ 1 Amp, resistive
Real-Time Clock Battery CR2032 (3V Cell)
Ethernet (wired) 10/100BASE-TX/FX; fully compliant to IEEE
802.3u standard
Tech Support 8:00am - 5:00pm Central Time
(800) 635-4269 www.winland.com
This guide provides basic setup instructions for the EA800-ip
Critical Environment Monitoring System and associated
sensors. Installers should refer to the Installation Manual
(found on-line at www.winland.com) for more
information, specifications, and to become familiar with the
device features. The device allows connection of up to 4 wired
and 8 wireless sensors and has 8 assignable dry contact alarm
loop connections.
Cloud Based Monitoring: The EA800-ip utilizes a cloud
computing architecture, no client software is required.
This version describes features only available on the INSIGHT
system using the firmware version C15f or higher.
S
PECIFICATIONS
©6
RJ
“Hereby Winland Electronics, Inc. declares that this environmental
monitoring equipment is in compliance with the essential
requirements and other relevant provisions of Directives 2014/53/
EU; 2014/30/EU; 2014/35/EU; 2011/65/EU. The declaration of
conformity may be consulted at: https://www.winland.com/
resources/regulatory-compliance/D-037-0010.pdf".