Cold location controller for conventional plants, up to 4 control circuits (evaporator)
4 CRC-XP_V2.92_PI_2019-03_EN
Subject to technical modifications
CRC-XP
Fig. 3: Dimensions
For wiring of the data lines, we recommend the use of standard telephone lines 2x2x0.8ø. up to
lengths of 100m. The shielding must be grounded in the control cabinet. For cable lengths from 100m
to 400m, shielded lines with braided sheathing should be used.
Sensor extension
For sensor extensions, it is recommended that sheathed cable be laid.
1.5 Technical data
• You can find more information about the device in the Wurm Infocenter.
Cable length Cross section
up to 100m 0.75mm²
up to 400m 1.5mm²
Power supply 230V~, +10% / -15%, approx. 5VA
Temperature sensor 4 x TRK277, T3000, T2015, DGF, K243, TF 201 / TF 231
Digital inputs 4 x potential-free
Output relay 4 x relay 230V~, normally open contacts, 230V~, 4(2)A
Temperature control Thermostat method
Defrost Forced air, electric, hot gas, cold gas
Central unit Single-chip microcomputer, data memory and quartz clock with
5000h power reserve
Monitoring system Monitoring of connected sensors, self-monitoring of data mem-
ory and microcomputer
Communication 3-wire CAN bus interface with integrated power supply, galvani-
cally isolated, service socket
Dimensions (WxHxD) 106 x 90 x 58mm (DIN 43880)
Fastening Top-hat rail TH 35-15 or TH 35-7.5 (DIN EN 60715)
Ambient temperature Operation: 0...+55°C, storage: -25...+70°C
Weight Approx. 450g
CE conformity
- 2014/30/EU (EMC Directive)
- 2014/35/EU (Low Voltage Directive)
EAC conformity
- TR CU 004/2011
- TR CU 020/2011
RoHS II
Valid from Version 2.92