ITALIANO5. PROGRAMMAZIONE
5.3 Applicazione 4-20mA metri
SONDA 4-20 mA
5.00 m
SONDA 4-20 mA
5.00 m
SERVE AD IMPOSTARE IL FONDO
SCALA DELLA SONDA UTILIZZATA
LIVELLO MINIMO
0.20 m
LIVELLO MINIMO
0.20 m
SERVE AD IMPOSTARE IL LIVELLO
DI ACQUA SOTTO IL QUALE LA
CENTRALINA SPEGNE I MOTORI
LIVELLO MAX 1
0.50 m
LIVELLO MAX 1
0.50 m
RANGE 0.10 ÷ 24.90m
LIVELLO ALLARME
1.00 m
LIVELLO ALLARME
1.00 m
SERVE AD IMPOSTARE IL LIVELLO
DI ACQUA SOPRA IL QUALE LA
CENTRALINA ABILITA L’USCITA
ALLARME
RANGE 1.0 ÷ 25.0m RANGE 0.05 ÷ 24.85m
SERVE AD IMPOSTARE IL LIVELLO
DI ACQUA SOPRA IL QUALE LA
CENTRALINA AVVIA IL PRIMO MOTORE
RANGE 0.20 ÷ 25m
5.1
LIVELLO MAX 2
0.80 m
LIVELLO MAX 2
0.80 m
SERVE AD IMPOSTARE IL LIVELLO
DI ACQUA SOPRA IL QUALE LA
CENTRALINA AVVIA IL SECONDO
MOTORE
RANGE 0.15 ÷ 24.95m
11
PREMUTO PER PIÚ DI 1s SI ESCE
DAL SETUP E SI SALVANO I
PARAMETRI IN MEMORIA
PREMUTO SI VISUALIZZA LA
RESTANTE PARTE DEI PARAMETRI
VEDI CAPITOLO 5.4