EasyManua.ls Logo

XOLTA BAT-5 - Modularity and Scalability of XOLTA BAT-5 and XOLTA BAT-10

XOLTA BAT-5
17 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
© 2021 by XOLTA
9
Figure 2.1:
Illustration of
maximizing self-
consumption in the
most optimal situation
2.4 Modularity and scalability of XOLTA BAT-5 and XOLTA BAT-10
XOLTA BAT-5 and XOLTA BAT-10 can be connected in parallel on the AC side to meet higher battery power
and/or energy requirements. The parallel connection also enhances system reliability and availability.
In the parallel operation, the following scenario is possible:
XOLTA BAT-5 and/or XOLTA BAT-10 systems work as one unit by equally sharing charge/discharge power;
Up to 3 XOLTA BAT-5 or up to 3 XOLTA BAT-10 battery systems can be connected on the AC side (both on
the same grid phase or the different grid phases). The resulting battery power and energy capability are
presented in Table 2.1 (XOLTA BAT-5) and in Table 2.2 ( XOLTA BAT-10).
Table 2.1: Battery
power and energy for
a different number
of parallel-connected
XOLTA BAT-5 battery
systems.
Table 2.2: Battery
power and energy for
a different number
of parallel-connected
XOLTA BAT-10
battery systems.
E
nergy shi
f
ted by batter
y
Even
i
n
g
N
oonMorn
i
n
g
T
im
e
S
hi
ft
S
olar production
Consum
p
t
i
on
BAT-5 UNITS 1 2 3
Nominal effect (kW) 3.6 7.2 10.8
Nominal energy (kWh) 5 10 15
Usable energy (kWh) 4.5 9 13.5
Connection 1P+N+E 2P+N+E 3P+N+E
BAT-10 UNITS 1 2 3
Nominal effect (kW) 3.6 7.2 10.8
Nominal energy (kWh) 10 20 30
Usable energy (kWh) 9 18 27
Connection 1P+N+E 2P+N+E 3P+N+E