EasyManuals Logo

Xtralis VESDA VLC-505 Product Guide

Xtralis VESDA VLC-505
48 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #19 background imageLoading...
Page #19 background image
VESDA by Xtralis VESDA VLC-EX Product Guide
www.xtralis.com 11
3.4 Default Settings
Table 3-3: Default values for the VESDA VLC-EX detector
Parameter Default Values Range Access Level
Minimum Maximum
Event Log - Events
l Smoke Level
Enabled N/A N/A Adm
l Alarms
Enabled N/A N/A Adm
l Faults
Enabled N/A N/A Adm
l User Action
Enabled N/A N/A Adm
Fire Threshold 0.2% obs/m
(0.062% obs/ft)
0.015% obs/m
(0.0046% obs/ft)
20% obs/m
(6.25% obs/ft)
Adm
Pre-Alarm Threshold 0.14% obs/m
(0.044% obs/ft)
0.010% obs/m
(0.0031 obs/ft)
1.995% obs/m
(0.6234% obs/ft)
Adm
Alert Threshold 0.08% obs/m
(0.025% obs/ft)
0.005% obs/m
(0.0015% obs/ft)
1.990% obs/m
(0.6218% obs/ft)
Adm
Alarm Delays…Fire 10 Seconds 0 Seconds 60 Seconds Adm
Alarm Delays…Pre-
Alarm
10 Seconds 0 Seconds 60 Seconds Adm
Alarm Delays…Alert 10 Seconds 0 Seconds 60 Seconds Adm
Delay Times Simultaneous Simultaneous Cumulative Adm
Instantaneous Fire Disabled N/A N/A Adm
AutoLearn 14 days
0 Hours
0 Minutes
0 days
0 Hours
15 Minutes
15 days
23 Hours
59 Minutes
Adm
Air flow Thresholds:
l High Urgent
l High Minor
l Low Minor
l Low Urgent
l 130%
l 120%
l 80%
l 70%
l 105%
l 105%
l 25%
l 25%
l 200%
l 200%
l 95%
l 95%
Adm
Communications:
l Open-ended loop
l Preferred Port
l Network Delay
l Health Check
l None
l A
l 15 seconds
l 45 seconds
l N/A
l N/A
l 10 seconds
l 40 seconds
l N/A
l N/A
l 45 seconds
l 60 seconds
DST
Device ID Name/Location N/A N/A Adm
Faults Latched Latched N/A N/A Adm
Filter Service Interval 731 days (2 years) 1 day (Dependent
up on environment)
3655 days (10
years)
Adm

Other manuals for Xtralis VESDA VLC-505

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Xtralis VESDA VLC-505 and is the answer not in the manual?

Xtralis VESDA VLC-505 Specifications

General IconGeneral
BrandXtralis
ModelVESDA VLC-505
CategorySecurity Sensors
LanguageEnglish

Related product manuals