en - Original instructions
56
• Observe the accident prevention
regulations in force.
• Use suitable equipment and pro-
tective devices.
• Always refer to the local regula-
tions, legislation and codes in force
regarding the selection of the in-
stallation site, plumbing and power
11.1
General maintenance
Before any servicing or maintenance,
disconnect the system from the power
supply and wait at least 2 minutes be-
fore starting work on or in the unit.
Turn off and unplug the system before
installing the unit or carrying out
maintenance.
• The Q-SMART control panel does not require
any routine maintenance when used within
the limits that are indicated in the
• Technical data.
• It is advisable to periodically check correct
triggering of the high sensitivity differential
switch (30 mA) [RCD, residual current device]
suited to the ground fault current.
12 Troubleshooting
Introduction
In addition to the alarm troubleshooting guide in
the List of alarms (sections
7 and 9), we also pro-
vide a guide for troubleshooting other possible
problems.
12.1
Faults, causes, and remedies
The pump does not run, the main switch is on.
supply
Restore the power supply and
check that the mains connec-
overload
Reset the overload circuit
breaker.
protective
Reset the differential protec-
tion.
faulty.
Replace the capacitor if it is an
external one. Contact the local
sales and service representa-
tive if it is an internal capaci-
The pump starts up but blows the converter
fuse
cable, short cir-
cu
the thermal protec-
tor or fuses are not
suited to the motor
components as neces-
sary.
Triggered thermal
overload switches
on single-phase
motors due to ex-
ditions of the pump.
The utilities are closed and the electric pump
runs at intermittent speeds
of the non-return
valve or out of the
cate the leaks.
Repair or replace the
components.
with broken dia-
not calibrated cor-
rectly in relation to
example, the value
is higher than the
pressure supplied
by the pump.
Recalibrate the threshold
and timing.
There could be a
problem with the
level float in the
intake tank.
tank.
There could be a
problem with the
level float in the
intake tank.
Check the pressure
switch and the intake
conditions (pressure).
The pump runs and there are vibrations in or
near the pump.
point is not cali-
brated correctly in
relation to the sys-
tem.
The value is below
the minimum pres-
sure that is sup-
Recalibrate the threshold
and timing.
The pump always runs at maximum speed.