7 Related Parameters
YASKAWA ELECTRIC TOBP C730600 35B YASKAWA AC Drive Option LED Operator Installation Manual 25
o2-05
Frequency
Reference
Setting Method
Selection
{{
Selects if the ENTER key press is required when
inputting the frequency reference by the operator
keypad.
0: Data/Enter key must be pressed to enter a
frequency reference.
1: Data/Enter key is not required. The frequency
reference is adjusted by the up and down arrow keys.
0
o2-06
Operation
Selection
when LED
Operator Option
is Disconnected
{{
Sets drive action when the LED Operator Option is
removed in LOCAL mode or with b1-02 = 0.
0: The drive will continue operation.
1: The drive will trigger a fault (oPr) and the motor
will coast to stop.
0
o3-01
Copy Function
Selection
{{
This parameter controls the copying of parameters to
and from the LED Operator Option.
0: COPY SELECT (no function)
1: All parameters are copied from the drive to the
LED Operator Option.
2: All parameters are copied from the LED Operator
Option to the drive.
3: Parameter settings in the drive are compared to
those in the LED Operator Option.
Note: When using the copy function, the drive model
number (o2-04), software number (U1-14), and
control method (A1-02) must match or an error will
occur.
0
o3-02 Copy Allowable
{{
Enables or disables reading of drive parameter
settings.
0: Disabled - Read not allowed
1: Enabled - Read allowed
0
<1> b1-01 = 4 and b1-02 = 3 are not compatible with the J1000 drive.
No. Name
Drive
Description Default
J1000