YORK® CEILING AND INLINE CENTRIFUGAL FANS, CI-SERIES
19
ENGINEERING SPECIFICATIONS
Model
CI1 = Low Flow Ceiling Fan
CIL1 / CIL2 = Ceiling Fan with Light
CIJ / CIT = Low Prole Ceiling Fan
CIF = Transfer Fan
UnitSize DriveType
0 = None D = Direct Drive
B = Belt Drive
MotorTap Enclosure
0 = None O = Open Drip Proof
Voltage Cycle
A = 115V 6 = 60 Hz
DischargeOrientation
R = Right Angle
Damper*
0 = None
BDD = Backdraft Damper
CurbCap
C = Curb Mounted
F = Flat Roof
S = Sloped Roof
W = Wall Mount
0 = None
BrickVent SteelGrille*
0 = None 0 = None
B = Brick Vent G = Steel Grille
SquaretoRoundTransition*
0 = None
T = Square to Round Transition
TopDischarge*
0 = None
T = TDA Kit Factory Installed
F = TDA Field Mount
VibrationIsolation
0 = None RH = Rubber Hanger
Transformer*
0 = None T = Transformer
SpeedController
0 = None L = Loose M = Mounted
Thermostat
0 = None
AirMinderSwitch
0 = None D = Air Minder Time Delay Switch
MotionSensor PilotLight
0 = None 0 = None
M = Motion Sensor P = Pilot Light
* Does not apply to models CI1, CIL1, CIL2
CI1,CIL1,&CIL2
Direct drive ceiling and cabinet fan shall be model CI1 or CIL (1 or 2) and supplied by
YORK® by Johnson Controls.
Fan housings shall be painted steel and include integral backdraft damper which shall
be chatter proof. Face grille shall be of aerodynamic design and include an unbreakable
lens for use with a 100 watt (max) bulb (except CI1). Fans shall be provided with cord,
plug and receptacle inside the housing. Entire fan, motor and wheel assembly shall be
removable. Fans shall have a forward curved centrifugal wheel. Fan motors shall be
positively cooled, have thermal overload protection, be suitably grounded and mounted
on vibration isolators.
Each fan shall bear the AMCA Licensed Rating Seal for Air and Sound Performance and
shall be UL507.
CIJ&CIT
All ceiling and/or wall mounted fans indicated on the plans and schedule shall be models
CIJ and/or CIT by YORK® by Johnson Controls.
Air deliveries and maximum sone levels shall be as indicated on the plans. Fans shall
be listed with Underwriters Laboratories. Fans shall feature true steel centrifugal wheels
and the galvanized steel fan casing shall incorporate an integral backdraft damper.
Motor speed shall not exceed listed RPM. Grille shall be of white egg-crate shape
design, comply with OSHA requirements and provide 85% free open area. Terminal box
shall be provided with cord, plug and receptacle. Entire fan, motor and wheel assembly
shall be removable without disturbing the housing.
Each fan shall be UL705 and UL507 Listed.
CIF
Direct drive axial room-to-room fan shall be model CIF, manufactured by YORK® by
Johnson Controls.
Fan housing shall be galvanized steel and shall include an adjustable sleeve to
accommodate various wall thicknesses. Two-faced grilles shall be of aerodynamic white
egg crate design and provide 85% free area. Entire fan, motor and propeller assembly
shall be removable. Propellers shall be die formed aluminum. Fan motor shall be
permanently lubricated, positively cooled, and have thermal overload protection. Fans
shall be provided with cord, plug, speed controller and receptacle factory installed inside
the housing.
Each fan shall bear the AMCA Licensed Ratings Seal for Air Performance, and shall be
UL705 and UL507.