567175-YTG-E-0512
Johnson Controls Unitary Products 21
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 °F), sensible capacity increases by 1060 BTUH per 1000 CFM per
degree above the listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
Continued on next page.
COOLING PERFORMANCE DATA
OUTDOOR UNIT MODEL NO. CZF04213(C)
INDOOR COIL MODEL NO. FC/MC62D
CONDENSER
ENTERING AIR
TEMPERATURE
ID CFM
1200 1400 1600
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
65
T.C. 39.4 42.1 42.1 46.0 49.2 41.2 42.7 42.7 47.0 50.4 43.0 43.3 43.2 48.0 51.7
S.C. 39.4 35.7 30.5 30.5 24.0 41.2 38.3 32.2 32.5 25.2 42.9 41.0 34.0 34.5 26.4
KW 2.43 2.44 2.43 2.45 2.46 2.51 2.52 2.50 2.53 2.53 2.59 2.60 2.58 2.61 2.61
75
T.C. 38.5 40.5 40.5 44.3 47.6 40.1 41.2 41.1 45.2 48.7 41.8 41.9 41.7 46.0 49.7
S.C. 38.5 35.2 29.9 29.8 23.5 40.1 37.8 31.7 31.8 24.7 41.8 40.4 33.6 33.7 25.9
KW 2.73 2.74 2.73 2.73 2.74 2.81 2.82 2.81 2.81 2.82 2.89 2.90 2.88 2.89 2.90
85
T.C. 37.6 38.9 38.8 42.7 46.1 39.0 39.7 39.5 43.3 46.9 40.5 40.4 40.2 44.0 47.7
S.C. 37.6 34.7 29.2 29.1 23.0 39.0 37.3 31.2 31.0 24.2 40.5 39.8 33.2 32.9 25.5
KW 3.03 3.04 3.04 3.02 3.03 3.11 3.11 3.11 3.10 3.11 3.19 3.19 3.18 3.18 3.19
95
T.C. 36.6 37.3 37.1 41.0 44.5 38.0 38.1 37.9 41.5 45.1 39.3 39.0 38.7 42.0 45.7
S.C. 36.6 34.2 28.6 28.3 22.5 38.0 36.7 30.7 30.2 23.7 39.3 39.0 32.7 32.1 25.0
KW 3.34 3.34 3.34 3.31 3.31 3.41 3.41 3.41 3.39 3.39 3.49 3.49 3.48 3.46 3.48
105
T.C. 34.8 35.1 34.9 38.4 42.0 36.1 35.9 35.6 38.9 42.5 37.4 36.8 36.3 39.4 43.1
S.C. 34.8 33.1 27.6 27.3 21.6 36.1 35.1 29.7 29.2 22.8 37.4 36.8 31.8 31.1 24.1
KW 3.89 3.88 3.87 3.80 3.78 3.94 3.94 3.93 3.87 3.85 3.99 4.00 3.99 3.94 3.93
115
T.C. 33.0 32.9 32.7 35.9 39.5 34.3 33.8 33.3 36.4 40.0 35.5 34.6 34.0 36.8 40.6
S.C. 33.0 31.9 26.7 26.4 20.7 34.3 33.5 28.8 28.3 22.0 35.5 34.6 30.8 30.1 23.2
KW 4.42 4.41 4.38 4.27 4.24 4.45 4.45 4.44 4.34 4.30 4.49 4.49 4.49 4.40 4.36
125
T.C. 31.3 30.8 30.5 33.4 37.0 32.4 31.6 31.0 33.8 37.5 33.6 32.4 31.6 34.3 38.0
S.C. 31.3 30.8 25.8 25.4 19.8 32.4 31.6 27.8 27.3 21.1 33.6 32.4 29.9 29.2 22.4
KW 4.96 4.94 4.90 4.75 4.69 4.97 4.96 4.94 4.81 4.74 4.98 4.99 4.98 4.86 4.80
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT. KW VALUES ARE FOR THE SYSTEM (OUTDOOR + INDOOR).
Air Handlers Coils
T.C. S.C. KW
– FC/MC/PC60 1.00 1.00 1.02
– FC64 1.02 1.05 1.00
– HD60 1.01 1.02 1.01
– UC60 0.98 0.98 1.02
AHE42D – 0.98 1.01 0.92
AHE48D – 1.01 1.03 0.94
AHE60D – 1.02 1.06 0.91
AHP48 – 1.00 1.03 1.00
AHP60 – 1.01 1.04 0.95
AHR42C – 0.96 1.00 1.00
AHR48D – 0.99 0.99 1.03
AHR60D – 1.00 1.02 1.00
AV*48 – 1.01 1.03 0.94
AV*60 – 1.01 1.03 0.94
AHX42 – 0.98 1.00 0.90
AHX48 – 1.02 1.07 0.93
AHX60 – 1.02 1.06 0.95
F6FP042 – 0.98 1.01 0.92
F6FP048 – 1.00 1.01 0.94
F6FP060 – 1.04 1.07 0.96
F4FV060 – 0.99 1.00 0.93
MV16C FC/MC43C 0.96 0.98 0.93
MV16C FC/MC48C 0.98 0.98 0.92
MV20D FC/MC48D 0.99 1.03 0.91
MV16C FC/MC60C 1.01 1.02 0.95
MV20D FC/MC60D 1.01 1.02 0.94
MV20D FC/MC62D 1.02 1.06 0.95
MV20D FC64D 1.04 1.07 0.92
MX16C FC/MC43C 0.96 0.99 0.93
MX16C FC/MC48C 0.98 0.99 0.89
MX20D FC/MC48D 0.98 1.01 0.90
MX16C FC/MC60C 1.02 1.05 0.95
MX20D FC/MC60D 1.04 1.07 0.94
MX20D FC/MC62D 1.05 1.09 0.93
MX20D FC64D 1.07 1.13 0.94