036-21318-002 Rev. A (0106)
Unitary Products Group 23
Multipliers for determining the performance with other indoor sections.
HEATING PERFORMANCE DATA
CONDENSING UNIT MODEL NO EABA-F030S
EVAPORATOR COIL MODEL NO F2RP/F2FP036
AIR TEMP.
ENTERING
OUTDOOR
UNIT
AIR TEMP.
ENTERING
INDOOR
COIL
ID CFM
850 1050 1250
MBTUH KW C.O.P. MBTUH KW C.O.P. MBTUH KW C.O.P.
60
60 35.42.723.8235.72.713.8735.92.693.91
70 33.92.823.5335.12.833.6435.72.843.69
80 32.52.903.2934.72.933.4835.62.953.54
47
60 29.62.633.3129.92.633.3430.12.633.35
70 28.02.723.0229.02.743.1029.52.763.14
80 26.52.802.7728.22.842.9229.02.872.96
40
60 24.72.502.9025.42.542.9425.62.562.93
70 23.32.602.6324.12.632.6924.42.662.69
80 22.02.712.3822.92.732.4623.22.762.47
30
60 21.52.382.6522.32.412.7222.72.442.73
70 19.72.432.3720.62.472.4521.12.512.47
80 17.92.512.0918.92.562.1619.52.612.19
17
60 17.52.362.1717.72.402.1718.02.472.14
70 15.82.421.9116.32.471.9416.72.531.94
80 14.12.491.6714.82.531.7215.42.591.74
10
60 14.42.181.9415.22.232.0015.72.292.01
70 13.02.221.7213.62.271.7714.22.331.79
80 11.6 2.25 1.51 12.0 2.30 1.53 12.6 2.36 1.57
NOTE:
ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Air Handler Coil
MBH KW COP
N1AHB1206 G2FD030(S,H)17 1.01 1.01 0.99
F2RP/F2FP030 0.99 0.99 1.00
G2FD030(S,H)17 1.01 1.01 0.99
G2FD035(S,H)14 1.01 1.01 0.99
G2FD036(S,H)17 1.01 1.02 1.00
G2FD036(S,H)21 1.02 1.02 1.00
G1HD036 1.02 1.02 1.00
G1NA030S17H 1.01 1.02 0.99
G1NA030S21B 1.01 1.02 0.99
G1UA03614 1.01 1.02 1.00
G1FA03614 1.01 1.02 1.00
G1UA036S17,21 1.01 1.01 0.99
G1FA036S17,21 1.01 1.01 0.99