036-21318-002 Rev. A (0106)
28 Unitary Products Group
Multipliers for determining the performance with other indoor sections.
HEATING PERFORMANCE DATA
CONDENSING UNIT MODEL NO EABA-(T,W)060S
EVAPORATOR COIL MODEL NO G2FD060(S,H)24
AIR TEMP.
ENTERING
OUTDOOR
UNIT
AIR TEMP.
ENTERING
INDOOR
COIL
ID CFM
1600 1800 2000
MBTUH KW C.O.P. MBTUH KW C.O.P. MBTUH KW C.O.P.
60
60 63.65.093.6761.94.983.6460.14.873.62
70 64.85.333.5663.55.183.5962.25.043.62
80 65.95.603.4565.15.393.5464.25.203.62
47
60 56.94.154.0355.74.024.0654.43.904.10
70 58.34.623.7058.04.543.7556.34.353.80
80 59.75.193.3859.05.033.4458.24.883.50
40
60 54.54.053.9553.33.933.9752.03.814.00
70 53.74.413.5753.44.323.6353.24.223.69
80 52.94.873.1953.64.783.2954.34.713.38
30
60 49.63.893.7449.83.803.8449.93.723.93
70 47.74.183.3448.04.103.4448.44.023.53
80 45.84.572.9446.34.473.0446.84.393.13
17
60 40.63.563.3441.03.513.4241.33.463.50
70 38.83.862.9439.23.803.0239.73.743.11
80 36.94.262.5437.54.182.6338.04.102.71
10
60 36.3 3.53 3.01 36.7 3.46 3.11 37.1 3.38 3.21
70 34.33.822.6334.73.742.7235.23.672.81
80 32.24.192.2532.74.122.3333.24.052.40
NOTE:
ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Air Handler Coil
MBH KW COP
N1AHD2046 G2FD060(S,H)24 1.00 1.00 1.00
F2FP060 G1FA060S21,24 1.01 1.03 0.95
G1FA060S21,24 1.00 1.00 1.00
G1UA060S21,24 1.00 1.00 1.00