036-21318-002 Rev. A (0106)
Unitary Products Group 3
PROCEDURES:
1. Unit factory charge listed on the unit nameplate includes refrigerant for the condenser, the smallest evaportor and for 15 feet of intercon-
necting line tubing.
2. Verify the orifice size and additional charge required for specific evaportor coil in the system using the above table.
3. Additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified in the table above.
4. Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + adder for
evaportor + adder for line set.
5. If the orifice in the evaportor was changed, verify the evaportor nameplate has been marked with the correct orifice size.
Additional R-22 Charge / Orifice Size for Various Matched Systems - 1 Phase
Outdoor Unit EBBA-F018S EBBA-F024S EABA-F030S EABA-F036S EABA-F042S EBBA-F048S EABA-F060S
Unit Orifice (s)
1
51,53 59,61 67, 69 67, 69, 71 75,78,81 81,84,87 87
Factory R-22 Charge, lbs-oz 4 - 14 5 - 0 4 - 8 5 - 12 6 - 9 8 - 3 9 - 8
Indoor Coil
Coil Orifice
2
System Orifice - Additional Charge, Oz
G2FD024S(H)17 61 53 + 12 59 + 9
G2FD030S(H)17 65 61 + 9 67 + 17
G2FD035S(H)14 65 61 + 9 67 + 17
G2FD036S(H)17/21 75 69 + 2
G2FD042S(H)21 78 71 + 7
G2FD046S(H)17 78 71 + 7 81 + 8
G2FD048S(H)21/24 84 81 + 15 87 + 6
G2FD060S(H)24 90 84 + 4
703
3
+ 1
G1HD024 59 53 + 13 59 + 9
G1HD036 69 67 + 22 69 + 4
G1HD048 81 81 + 10 84 + 6 -
G1HD060 93 84 + 0
703
3
+ 1
G1FA/G1UA024S14/17 59 53 + 10
G1FA/G1UA030S14 65 59 + 10
G1FA/G1UA036S14 73 - 67 + 17
G1FA/G1UA03617/21 73 61 + 9 67 + 15
G1FA/G1UA048S21/24 84 71 + 12 81 + 13 84 + 3
G1FA/G1UA060S24 90 84 + 4
703
3
+ 1
G1NA030S17H 57 53 + 0 59 + 0 69 + 0
G1NA030S21B 57 53 + 0 59 + 0 69 + 0
G1NA036S17L 71 67 + 7
G1NA048S21D 78 67 + 7 75 + 0 81 + 8
G1NA048S24P 78 75 + 0 81 + 8
G1NA060S24T 87 87 + 0
G1NF024SOF 63
59 + 0
4
—————
G1NF036SOF 67
69 + 0
4
67 + 7
4
———
G1NF048SOF 78
75 + 0
4
84 + 4
4
G1NF060SOF 87
87 + 0
4
F2RP/F2FP018 53 51 + 10
F2RP/F2FP024 61 51 + 21 59 + 9
F2RP/F2FP030 65 69 + 19
F2RP/F2FP036 75 69 + 23 71 + 4
F2RP/F2FP042 78 71 + 7 81 + 8
F2FP048 84 81 + 15 84 + 0
F2FP060 90 87 + 4
703
3
+ 1
FOOTNOTES:
1. These orifices are packed in the customer packet of each outdoor unit.
2. These orifices are factory mounted in the flow control device of each indoor coil.
3. TXV kit must be used with these coils to obtain system performance. (701,702,703 indicates 1TV07 ...series).
4. Systems matched with furnaces or air handlers not equipped with blower-off delays, may require blower Time Delay Kit #2FD0670224.