036-21320-002 Rev. A (1103)
12 Unitary Products Group
CP equals MBH output divided by (total KW input x 3.412).
HSPF (Heating Seasonal Performance Factor) is the total heating output during a normal annual usage period for heating divided by the total electric
power input during the same period.
— = Not Applicable.
ACCESSORIES
Refer to Price Manual for specific model numbers.
Start Assist Kit (2SA067*)
Blower Time Delay - Available to increase efficiency when
installed. Installs on indoor section and maintains blower for
approximately one minute after cooling thermostat has been
satisfied.
Hard Start Kits - Provides required starting torque for use
with Thermal Expansion Valve Kit.
Low Temperature Cutout (2LT06700224) - Prevents heat
pump operation below -10°F ambient temperature.
Compressor Blanket - Designed to further reduce the nor-
mal operating sound.
Add-on Fossil Fuel Control - Interface controls for use with
gas, oil furnaces and the heat pump system are available.
Thermal Expansion Valve Kit - 1TV0700 Series TXV kit
used to improve system performance.
Outdoor Thermostat (2TD06700124) - Provides additional
staging of supplemental electric heat.
Room Thermostats - A wide selection of matching thermo-
stats is available to provide features required for any installa-
tion.
2H/1C, manual change-over electronic non-programmable
thermostat.
3H/2C, non-programmable digital thermostat.
3H/2C, auto/manual changeover, electronic programmable,
7-day, hardwire thermostat.
* For the most current accessory information, refer to the
price book or consult factory.
SOUND RATINGS
*Rated in accordance with ARI Standard 270.
All dim ensions are in inches. They are subject to change without
notice. Certified dimensions will be provided upon request
.
EBBC-F060S
G8V***20UHC G1FA060S21 58.4 3.52 4.86 34.6 2.42 4.19 8.05 18.9 4.00 26.8 4.22 38.5 4.28 42.2 4.33 66.3 4.87
G9V***20DHD G2FD060
(S,H)2459.28.002.1735.42.344.438.0019.74.2527.64.4739.34.5343.04.5867.15.12
G9V***20UPC G1FA060S21 58.1 3.56 4.78 34.4 2.44 4.13 8.10 18.6 3.92 26.5 4.14 38.2 4.20 41.9 4.25 66.0 4.79
G9V***20UPD G1FA060S24 58.1 3.56 4.78 34.4 2.44 4.13 8.10 18.6 3.92 26.5 4.14 38.2 4.20 41.9 4.25 66.0 4.79
G9V***20UPD G2FD060
(S,H)2458.13.564.7834.42.444.138.1018.63.9226.54.1438.24.2041.94.2566.04.79
G9V***20UPD G2FD061H24 58.7 3.62 4.76 34.6 2.44 4.15 8.25 18.9 3.87 26.8 4.09 38.4 4.13 42.1 4.17 66.7 4.76
1. Rated CFM same as for cooling.
2. Heating MBH based on ARI standards of 70° DB entering indoor air, 72% RH outdoor air with 25 feet of interconnecting piping and no supplemental
electric heat operation.
3. Integrated heating capacities include the effect of defrost cycles in the temperature range where they occur.
HEATING PERFORMANCE - With Variable Speed Furnaces (Continued)
UNIT
MODEL
FURNACE
COIL
1
MODEL
ARI HEATING
2
OUTDOOR TEMP
3
47°F 17°F
HSP
F
-3°F 7°F 27°F 37°F 57°F
MBH COP KW MBH COP KW STD MBH KW MBH KW MBH KW MBH KW MBH
KW
UNIT MODEL
SOUND
RATINGS DECIBELS
018 80
024 80
030 80
036 80
042 80
048 80
060 80
UNIT
MODEL
DIMENSIONS
(INCHES)
REFRIGERANT
CONNECTION
LINE SIZE
A
1
1. Including Fan Guard.
B C Liquid Vapor
018 25 35 23
3/8”
3/4”024 27 37 27
030 27 37 27
036 33 37 27
7/8”042 33 37 27
048 32 43 32
060 32 43 32
7/8”
2
2. Three-phase uses 7/8”. Single-phase uses 1-1/8”.
1-1/8”
2
C
B
A