036-21320-002 Rev. A (1103)
Unitary Products Group 13
TYPICAL INSTALLATION - DRHS018 THRU 060
TYPICAL FIELD WIRING - 1 Phase Application
TYPICAL FIELD WIRING - 3 Phase Application
MINIMUM 18” SERVICE ACCESS
CLEARANCE ON ONE SIDE
60” OVERHEAD
CLEARANCE
10” CLEARANCE
COIL AREA
WEATHERPROOF
DISCONNECT
SWITCH
THERMOSTAT
TO FURNACE OR
AIR HANDLER
TERMINAL BLOCK
NEC CLASS 1 WIRING
NEC CLASS 2 WIRING
TO INDOOR COIL
SEAL OPENING(S) WITH
PERMAGUM OR EQUIVALENT
CONTROL ACCESS PANEL
NOTE: ALL OUTDOOR WIRING
MUST BE WEATHERPROOF.
THERMOSTAT
INDOOR UNIT
OUTDOOR UNIT
LOW VOLTAGE TERMINAL BLOCK
IN AIR HANDLER WITH ELECTRIC HEAT
3,4
DEFROST
CONTROL
1
FIELD
INSTALLED
JUMPER
DEHUMIDIFICATION CONTROL CONNECTION
(Humidistat* Jumper must be removed)
GND.
SCREW
CONTACTOR
T2
T1
L2
L1
M
R
LorX
Y
O
W
G
T
2
E
2
R
R
Y
Y
O
O
W2
W
W1
C
C
X/L
G
W1
BK
GND.
LUG
CIRCUIT
BREAKER***
POWER WIRING
24V CONTROL WIRING
(NEC CLASS 2)
JUMPER TERMINALS E AND W TOHEAT
ON FIRST STAGE DURING EMERGENCY HEAT.
1
2
TERMINAL NOT USED ON ALL THERMOSTATS.
POWER WIRING
208/230-1-60
230-1-50
3
CHECK THE LOW VOLTAGE TERMINAL BLOCK ON THE INDOOR UNIT FOR THE ACTUAL ARRANGEMENT OF THE TERMINALS.
4
CONNECT POWER WIRING TO TERMINAL BLOCK 3TB ON UNITS WITHOUT ELECTRIC HEAT OR CIRCUIT BREAKER.
BorC
ALL FIELD WIRING TO BE IN ACCORDANCE WITH ELECTRIC CODE (NEC) AND/OR LOCAL CODES
RED
BLK
YEL
ORG
BRN
PUR
WHT
CC
GRY
/66
5
GRAY FOR USE WITH OPTIONAL OUTDOOR THERMOSTAT KITS.
5
ALL FIELD WIRING TO BE IN ACCORDANCE WITH ELECTRIC CODE (NEC) AND/OR LOCAL CODES
POWER WIRING
208/230-3-60
460-3-60
CONTACTOR
TERMINALS
COIL
GND.
LUG
CYRGW
YRGW
POWER WIRING
CONTROL WIRING
FACTORY WIRING
24 VOLT CONTROL WIRING
MINIMUM 18 GA. WIRE
(NEC CLASS 2)
FURNACE OR AIR HANDLER TERMINAL BLOCK
ROOM THERMOSTAT
CONDENSING UNIT
ALL OUTDOOR WIRING MUST BE WEATHERPROOF. USE COPPER CONDUCTORS ONLY.
TERMINAL W IS ONLY
REQUIRED ON SYSTEMS
WITH HEAT.
*
*