036-21320-002 Rev. A (1103)
Unitary Products Group 27
Multipliers for determining the performance with other indoor sections.
HEATING PERFORMANCE DATA
CONDENSING UNIT MODEL NO EABC-(T,W)036S
EVAPORATOR COIL MODEL NO G1FA048S21
AIR TEMP.
ENTERING
OUTDOOR
UNIT
AIR TEMP.
ENTERING
INDOOR
COIL
ID CFM
1050 1250 1450
MBTUH KW C.O.P. MBTUH KW C.O.P. MBTUH KW C.O.P.
60
60 39.7 3.08 3.78 38.3 3.02 3.72 36.8 2.96 3.65
70 39.5 3.24 3.59 38.5 3.19 3.54 37.5 3.15 3.50
80 39.2 3.39 3.39 38.7 3.37 3.37 38.1 3.35 3.34
47
60 35.1 2.81 3.66 34.1 2.78 3.59 33.0 2.76 3.51
70 34.2 2.93 3.42 34.0 2.95 3.38 33.1 2.91 3.34
80 32.9 3.03 3.18 33.0 3.05 3.18 33.1 3.06 3.17
40
60 31.3 2.66 3.45 31.0 2.67 3.41 30.7 2.67 3.37
70 30.3 2.76 3.23 30.5 2.78 3.22 30.7 2.81 3.21
80 29.3 2.85 3.01 30.0 2.90 3.03 30.7 2.95 3.05
30
60 28.1 2.57 3.21 28.1 2.59 3.18 28.0 2.61 3.15
70 26.2 2.55 3.02 26.5 2.58 3.01 26.9 2.62 3.01
80 24.3 2.53 2.82 25.0 2.58 2.85 25.7 2.63 2.87
17
60 21.0 2.36 2.61 21.6 2.41 2.63 22.1 2.45 2.64
70 19.5 2.25 2.54 20.2 2.37 2.50 20.6 2.54 2.39
80 18.0 2.55 2.07 18.6 2.59 2.10 19.1 2.63 2.13
10
60 17.2 2.25 2.29 18.1 2.31 2.33 18.9 2.37 2.37
70 15.9 2.41 1.98 16.6 2.45 2.01 17.2 2.50 2.05
80 14.6 2.56 1.67 15.1 2.60 1.70 15.5 2.63 1.73
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Coil
MBH KW COP
G1UA048S21 1.00 1.00 1.00
G1HA048H21 0.99 0.99 0.99
G2FD048S(21,24) 1.01 1.00 1.01