036-21320-002 Rev. A (1103)
28 Unitary Products Group
Multipliers for determining the performance with other indoor sections.
HEATING PERFORMANCE DATA
CONDENSING UNIT MODEL NO EABC-F042S
EVAPORATOR COIL MODEL NO F2FP048
AIR TEMP.
ENTERING
OUTDOOR
UNIT
AIR TEMP.
ENTERING
INDOOR
COIL
ID CFM
1200 1400 1600
MBTUH KW C.O.P. MBTUH KW C.O.P. MBTUH KW C.O.P.
60
60 49.7 3.33 4.38 48.5 3.26 4.36 47.2 3.19 4.33
70 50.9 3.57 4.18 50.0 3.49 4.20 49.1 3.42 4.21
80 50.8 3.89 3.83 50.2 3.80 3.87 49.7 3.72 3.92
47
60 41.9 3.23 3.81 41.4 3.20 3.80 40.8 3.16 3.79
70 42.3 3.46 3.58 41.5 3.60 3.38 41.6 3.38 3.61
80 41.9 3.77 3.26 41.8 3.72 3.29 41.6 3.67 3.33
40
60 37.0 3.19 3.40 36.6 3.16 3.39 36.2 3.14 3.39
70 36.8 3.42 3.15 36.6 3.39 3.16 36.4 3.36 3.17
80 36.0 3.71 2.84 35.9 3.67 2.87 35.9 3.63 2.90
30
60 33.9 3.08 3.22 33.9 3.07 3.23 33.9 3.07 3.24
70 33.2 3.31 2.94 33.2 3.29 2.96 33.1 3.27 2.97
80 32.2 3.59 2.63 32.1 3.55 2.65 32.0 3.51 2.67
17
60 26.3 2.94 2.62 26.6 2.95 2.64 26.9 2.97 2.66
70 25.1 3.13 2.35 25.2 3.21 2.30 25.8 3.15 2.40
80 23.8 3.36 2.08 24.3 3.37 2.11 24.7 3.37 2.15
10
60 23.2 2.84 2.39 23.5 2.87 2.40 23.8 2.90 2.41
70 21.5 3.00 2.10 22.0 3.03 2.12 22.4 3.06 2.14
80 20.1 3.20 1.84 20.6 3.23 1.87 21.1 3.26 1.90
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Air Handler Coil
MBH KW COP
N1AHC1606 G2FD042(S,H)21 0.99 0.95 1.04
F2RP/F2FP042 0.99 0.94 1.05
N1VSC16 G2FD048
(S,H)21 1.00 1.00 1.00
G1FA048S21 1.00 0.97 1.03
G1HD048 1.00 0.98 1.02
G1NA048S21D 0.98 0.92 1.06
G1UA048S21 1.00 0.97 1.03
G2FD042
(S,H)21 0.99 0.95 1.04
G2FD048
(S,H)21,24 1.00 0.97 1.03
G2FD060
(S,H)24 1.00 0.99 1.01
G1HA036H17 0.97 0.93 1.03
Variable Speed
Furnace
Coil
T.C. S.C. KW
G8V***20UHC G1FA048S21 0.99 1.00 0.99
G8V***20UHC G2FD042
(S,H)21 0.98 0.98 1.00
G8V***20UHC G2FD048
(S,H)21 0.99 0.99 1.00
G9V***20DHD G2FD048
(S,H)24 0.96 0.97 1.00
G9V***16UPC G1FA048S21 0.99 1.00 0.99
G9V***16UPC G2FD042
(S,H)21 0.98 0.97 1.01
G9V***16UPC G2FD048
(S,H)21 1.00 0.98 1.02