JOHNSON CONTROLS
130
FORM 150.67-NM1
ISSUE DATE: 4/28/2017
SECTION 5 – TECHNICAL DATA
DIMENSIONS – YCAL0066 (SI)
NOTE:
Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable
operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airow
patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high-pressure safety cutouts;
however, the system designer must consider potential performance degradation. Recommended minimum clearances: front to wall – 2m; rear
to wall – 2m; cooler end to wall – 1.2m; coil end to wall – 2m; top – no obstructions allowed; distance between adjacent units – 3m. No more
than one adjacent wall may be higher than the unit. 1" nominal deection isolators (not shown) will increase overall unit height by 152mm.
1590
1572
880
401
252
1095
321
76 VICTAULIC (typ)
ELECTRICAL ACCESS
PANEL
2292 BASE WIDTH
LEFT END
LIQUID OUT
LIQUID IN
VIEW B-B
22 TYP.
100
82
171
BOTTOM OF PANEL
All dimensions are in mm unless specied otherwise.