EasyManua.ls Logo

York YCAL0019 - Page 56

York YCAL0019
230 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
JOHNSON CONTROLS
56
FORM 150.67-NM1
ISSUE DATE: 4/28/2017
SECTION 5 – TECHNICAL DATA
Single-Point Field Supplied Power Wiring (See Figure 12)
(One Field Provided Power Supply to the chiller. Field connections to Factory Provided Power Terminal Block (standard), Non-Fused
Disconnect Switch (optional) or Circuit Breaker (optional)).
ELECTRICAL DATA (ENGLISH)
YCAL0019_ – YCAL0066_ (CON’T.)
(Without Pump)
TABLE 7 – ELECTRICAL DATA (ENGLISH) (CONT.)
MODEL
YCAL
VOLT
60 Hz
MCA
1
MIN N/F
DISC
MDSW
2
D.E. FUSE CKT. BKR.
5
FIELD WIRING LUGS
6
TERMINAL BLOCK (std)
FIELD WIRING LUGS
6
NF DISC. SWITCH (opt)
FIELD WIRING LUGS
6
CIRCUIT BREAKER (opt)
MIN. MAX
4
MIN. MAX
LUGS/
PHASE
LUG WIRE RANGE
LUGS/
PHASE
LUG WIRE RANGE
LUGS/
PHASE
LUG WIRE RANGE
0056
200 268 400 300 300 300 300 1 6 AWG – 350 kcmil 2 *(2) 3/0 – 250 kcmil 2 *(2) 3/0 – 250 kcmil
230 267 400 300 300 300 300 1 6 AWG – 350 kcmil 2 *(2) 3/0 – 250 kcmil 2 *(2) 3/0 – 250 kcmil
380 171 200 200 200 200 200 1 14 AWG – 2/0 1 4 AWG – 300 kcmil 1 6 AWG – 350MCM
460 130 150 150 150 150 150 1 14 AWG – 2/0 1 4 AWG – 300 kcmil 1 6 AWG – 350MCM
575 112 150 125 125 125 125 1 14 AWG – 2/0 1 4 AWG – 300 kcmil 1 6 AWG – 350MCM
0066
200 324 400 350 400 350 400 1 4 AWG – 500 kcmil 1 250 kcmil – 500 kcmil 1 250 kcmil – 500 kcmil
230 301 400 350 350 350 350 1 4 AWG – 500 kcmil 1 250 kcmil – 500 kcmil 1 250 kcmil – 500 kcmil
380 175 200 200 200 200 200 1 6 AWG – 350 kcmil 1 6 AWG – 350 kcmil 1 6 AWG – 350MCM
460 143 200 175 175 175 175 1 6 AWG – 350 kcmil 1 6 AWG – 350 kcmil 1 6 AWG – 350MCM
575 115 150 125 125 125 125 1 6 AWG – 350 kcmil 1 6 AWG – 350 kcmil 1 6 AWG – 350MCM
* Panels will have (3) 250 KEMIL lug kit shipped loose to accommodate larger wire size if needed.

Table of Contents

Other manuals for York YCAL0019

Related product manuals