W. Remote Cooler: Manufacturer shall provide separately: chiller less evaporator, leaving
and return water sensors, and liquid line components (solenoid valves, lter driers,
sight glasses, and TXVs), as discrete elements of a complete factory system. Contrac-
tor shall be eld erect system and provide interconnecting refrigerant piping and wiring
in accordance with Manufacturer recommendations, and project plans and schedules.
Where not otherwise specied, Contractor provided system piping shall be in accor-
dance with applicable sections of ASHRAE Handbook.
X. Hot Gas By-Pass: Permits continuous, stable operation at capacities below the mini-
mum step of unloading to as low as 5% capacity (depending on both the unit & op-
erating conditions) by introducing an articial load on the cooler. Hot gas by-pass is
installed on only one refrigerant circuit (System #1).
Y. Microprocessor Membrane Keypad Graphics on in lieu of Standard English:
1. French language.
2. German language.
3. Spanish language.
4. Italian language.
Z. Thermal Storage: Leaving chilled liquid setpoint range for charge cycle from 25°F to
20°F minimum, with automatic reset of the leaving brine temperature up to 40°F above
the setpoint. (Works with Option T)
AA. R. Low Temperature Process Brine: Leaving chilled liquid setpoint range 20°F to 30°F.
AB. Chicago Code Relief Valves to meet Chicago Code requirements.
AC. Building Automation System (EMS) Reset Interface: Chiller to accept 4 to 20mA, 0 to
10 VDC, or discrete contact closure input to reset the leaving chilled liquid temperature.
AD. Sound Reduction (Factory-mounted):
1. Ultra quiet, low speed, reduced noise fans
2. Compressor Acoustic Sound Blankets
AE. Vibration Isolation (Field-Mounted):
1. Neoprene Pad Isolators.
2. 1 Inch Deection Spring Isolators: Level adjustable, spring and cage type isolators
for mounting under the unit base rails.
3. 2 Inch Deection Isolators: Level adjustable, restrained mounts in rugged welded
steel housing with vertical and horizontal limit stops. Housings shall be designed to
withstand a minimum 1.0g accelerated force in all directions to 2 inches.