JOHNSON CONTROLS
FORM 150.67-EG1 (219)
62
Unit Dimensions (Cont'd)
YCAL0022 SI
NOTE: All dimensions are in mm unless specied otherwise.
LEFT END
6 3/4"
3 1/4"
3 15/16"
BOTTOM OF PANEL
7/8" TYP.
VIEW B-B
POWER: SINGLE POINT SUPPLY WITH TERMINAL BLOCK
46 1/16"
45 1/4"
11 5/8"
2" DIA
(2) 3.0 X 1.50
RIGGING HOLES
BOTH ENDS
44 5/16"
BASE WIDTH
18 3/4"
11"
TO ACCESS PANEL 16 1/4"
8 5/16"
12 13/16"
8 5/16"
12 13/16"
B
B
2 1/4"
2" ANSI/AWWA C-606
CONN (typ)
IN
OUT
LD18691
NOTE:
Placement on a level surface free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable
operation, and east of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airow
patterns and possible diminished performance. YORK's unit controls will optimize operation without nuisance high-pressure safety cutouts;
however, the system designer must consider potential performance degradation. Recommended minimum clearances: front to wall - 2m;
rear to wall - 2m; cooler end to wall - 1.2m; coil end to wall - 2m; top - no obstructions allowed; distance between adjacent units - 3m. No
more than one adjacent wall may be higher than the unit. 1" nominal deection isolators (not shown) will increase overall unit height by 152.