EasyManua.ls Logo

York YCM Series - 3-2 Pre-Startup Checks

York YCM Series
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
N
L1 L2 L3
工厂配置
用户自配
PE
PE
PE
N
PE L1 L3L2
380V.3~ N.PE.50Hz 380V.3~ N.PE.50Hz
3-2 Check Before Startup
After air handling unit is installed, before starting-up and testing, please check the following items firstly:
1. Check air handling unit to find whether components are loosened or not;
2. Check earth-grounding wire to find whether it is connected well or not;
3. Before starting fan, check air duct to find whether it is ventilated or not; Damper should not be in off position;
4. Check flexible duct or duct connecting apparatus;
5. All water pipes are connected well;
6. Check power supply, including short-circuit and circuit-break protection;
7. Drain pipes have been connected correctly;
8. Filter has been installed correctly without any building fragments and dust on it;
9. Check motor and fan bearing to find whether they run freely or not;
10. Hydraulic pressure testing and ventilation testing.
11. The wooden support under the fan base is taken out or not.
Fan
-Shut off switch before checking internal parts of fan;
-Check fan and motor components to find whether anti-vibration and flexible connection apparatus operate freely or not;
-Air handling unit is driven by belt and pulley. Please check tension degree of belt. The tension degree of belt is as follows
(Following picture);
-Check electrical connection apparatus of motor to find whether it accords with the provided wiring diagram or not;
-Check nameplate of motor to find whether its voltage, phase and electrical circuit accord with power on the spot or not;
-Check the running current of motor by ammeter; Compare it with the data on nameplate of motor.
Power of motor: Less than or equal to 5.5KW Direct
Startup Principle Diagram
Power of motor: Bigger than or equal to 7.5KW Y-Δ
Startup Principle Diagram
29
Starting &
Running