Model
(Capacity Btu/h)
The range of
static pressure
Function code set
9K/12K
0-50Pa
1-50more than 50 is 50 Pa,
[default: 0(0Pa)]
24K
0-80Pa
1-80more than 80 is 80 Pa,
[default: 0(25Pa)]
36K
0-120Pa
1-120more than 120 is 120 Pa,
[default: 0(47Pa)]
42K/48K/55K 0-120Pa
1-120more than 120 is 120 Pa,
[default: 0(60Pa)]
Parameter Code
Function Code
Function Revise Indicator
M
T
V
V
JCSA21NEWH
Static pressure setting(JCSA21NEWH):
Hold down “ ”,“ ”and “ ”buttons for 5 seconds, symbol and parameter code blinking at the
same time.
Press“ / ”button to adjust parameter number until display “17”, and press “ ”button to entering
system parameter adaption state, symbol stop blinking.
Select desired parameter code 10 by pressing“ / ”button , and press " " button to confirm.
Select desired function code to rewrite the parameter values by pressing “ / button , and press
" " button to confirm.
Press “ ”button to quit.
1
2
3
4
5
V
V
V
V
V
V
V
V
M
T
M
T
M
T
If you still have any trouble, please contact local technical service center of our company for further
information.
Installation and MaintenanceInstallation and Maintenance
12
6.2 Change of Static Pressure
The static pressure outside the indoor unit can be chosen.
WHT
RED
Fan motor
Low static pressure
High static pressure
6.2.1 For AC MOTOR type:
6.2.2 For DC MOTOR type :
You can change the static pressure by changing the fan motor terminal which refer to following Fig6.2.1.
The static pressure can be freely adjusted by using specific wired remote controller.
Note:
Fig 6.2.1
*: Default Settings is low static pressure by factory.
The noise under high static pressure is higher than low static pressure .
Model
High static
pressure
Low static
pressure
18K
30Pa
10Pa*

Related product manuals