148 Johnson Controls Ducted Systems
PERFORMANCE DATA - 3 TON
CONDENSER-ONLY DATA (OUTDOOR UNIT)
MODEL
SATURATED SUCTION
AT COMPRESSOR
Outdoor Ambient Temperature
55 °F 65 °F 75 °F 85 °F 95 °F 105 °F 115 °F 125 °F
T (°F) P (PSIG) MBH KW MBH KW MBH KW MBH KW MBH KW MBH KW MBH KW MBH KW
YFK36B21S
(Stage 2)
35 107 33.0 1.75 31.3 1.93 29.7 2.11 28.1 2.32 26.3 2.56 24.5 2.84 22.6 3.18 20.5 3.57
40 118 36.3 1.75 34.5 1.92 32.8 2.11 31.0 2.31 29.1 2.54 27.1 2.83 25.0 3.17 22.8 3.55
45 130 39.9 1.75 38.0 1.92 36.0 2.11 34.1 2.30 32.1 2.53 29.9 2.81 27.7 3.15 25.3 3.53
50 142 43.5 1.76 41.6 1.92 39.6 2.10 37.5 2.30 35.3 2.51 33.0 2.79 30.5 3.12 27.9 3.50
55 156 47.6 1.78 45.5 1.92 43.3 2.10 41.0 2.29 38.7 2.50 36.2 2.77 33.6 3.10 30.7 3.47
YFK36B21S
(Stage 1)
35 107 21.7 1.32 19.7 1.53 18.3 1.75 17.2 1.97 16.1 2.21 14.7 2.50 13.6 2.87 10.6 3.23
40 118 24.6 1.25 22.2 1.48 20.5 1.71 19.2 1.93 17.9 2.18 16.5 2.46 14.8 2.79 12.6 3.18
45 130 27.9 1.17 25.0 1.42 23.0 1.65 21.4 1.89 20.0 2.13 18.5 2.42 16.8 2.75 14.6 3.12
50 142 31.6 1.09 28.2 1.35 25.8 1.60 23.9 1.83 22.2 2.09 20.6 2.38 18.8 2.70 16.7 3.07
55 156 35.8 1.00 31.9 1.27 28.9 1.52 26.6 1.78 24.7 2.04 22.9 2.32 21.0 2.65 18.8 3.01
Notes:
1. For Outdoor Unit (Condenser) performance only. Data does not include the effects of air handler power or heat.
2. Performance based on 15°F subcooling and 15°F superheat at the Outdoor Unit base valves.
a. Increase capacity by 1% for each 2°F increase in subcooling.
b. Decrease capacity by 1% for each 2°F decrease in subcooling.
3. Maximum recommended condensing temperature is 140°F.
COOLING PERFORMANCE DATA
OUTDOOR UNIT MODEL NO. YFK36B21S
INDOOR COIL MODEL NO. CF64DXA1
AIR TEMPERATURE
ENTERING
OUTDOOR UNIT (°F)
ID CFM 950 1200 1450
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
55
T.C. 33.4 36.3 36.0 37.7 38.5 34.4 36.8 36.8 38.0 39.0 35.4 37.4 37.5 38.4 39.4
S.C. 33.4 29.6 25.2 23.9 18.2 34.4 30.9 26.6 24.5 18.4 35.4 32.2 28.0 25.1 18.6
KW 1.92 1.93 1.94 1.94 1.94 2.03 2.03 2.04 2.04 2.04 2.14 2.14 2.14 2.15 2.14
65
T.C. 32.6 35.1 35.1 37.5 39.5 34.2 36.1 36.1 38.3 40.3 35.8 37.1 37.1 39.2 41.0
S.C. 32.6 29.3 24.9 24.2 18.8 34.2 31.7 26.8 25.6 19.5 35.8 34.0 28.8 27.0 20.1
KW 2.11 2.12 2.13 2.13 2.15 2.22 2.23 2.23 2.24 2.25 2.33 2.33 2.34 2.34 2.35
75
T.C. 31.9 33.9 34.1 37.3 40.5 34.0 35.4 35.4 38.6 41.5 36.2 36.8 36.8 39.9 42.5
S.C. 31.9 29.1 24.5 24.4 19.5 34.0 32.4 27.1 26.6 20.6 36.2 35.8 29.7 28.9 21.6
KW 2.30 2.31 2.32 2.33 2.35 2.42 2.42 2.43 2.44 2.45 2.53 2.53 2.53 2.54 2.56
85
T.C. 30.9 32.7 32.7 35.9 39.1 32.9 34.0 34.0 37.2 40.2 34.9 35.3 35.2 38.5 41.3
S.C. 30.9 28.6 24.0 23.9 19.1 32.9 31.9 26.6 26.2 20.1 34.9 35.2 29.2 28.5 21.1
KW 2.56 2.55 2.56 2.57 2.59 2.67 2.66 2.67 2.68 2.70 2.78 2.77 2.78 2.79 2.81
95
T.C. 30.0 31.5 31.4 34.6 37.7 31.8 32.6
32.5 35.8 38.9 33.6 33.8 33.7 37.0 40.1
S.C. 30.0 28.2 23.5 23.4 18.7 31.8 31.4 26.1 25.8 19.7 33.6 33.8 28.7 28.2 20.7
KW 2.81 2.80 2.81 2.81 2.84 2.91 2.90 2.92 2.92 2.95 3.02 3.01 3.02 3.03 3.05
105
T.C. 28.5 29.6 29.6 32.5 35.5 30.2 30.7 30.6 33.6 36.7 31.8 31.8 31.6 34.8 37.8
S.C. 28.5 27.3 22.7 22.5 17.8 30.2 29.9 25.3 24.9 18.8 31.8 31.8 27.9 27.3 19.8
KW 3.15 3.14 3.16 3.16 3.19 3.26 3.25 3.26 3.27 3.29 3.37 3.36 3.37 3.38 3.40
115
T.C. 27.1 27.7 27.8 30.4 33.4 28.6 28.8 28.7 31.5 34.5 30.1 29.9 29.6 32.6 35.5
S.C. 27.1 26.4 21.9 21.6 17.0 28.6 28.5 24.5 24.0 17.9 30.1 29.9 27.1 26.3 18.9
KW 3.49 3.48 3.49 3.50 3.52 3.60 3.59 3.60 3.61 3.63 3.70 3.70 3.71 3.72 3.73
125
T.C. 25.6 25.8 26.1 28.4 31.3 27.0 26.9 26.9 29.4 32.3 28.4 27.9 27.7 30.4 33.3
S.C. 25.6 25.5 21.1 20.8 16.1 27.0 26.9 23.7 23.1 17.1 28.4 27.9 26.3 25.4 18.0
KW 3.82 3.82 3.83 3.84 3.86 3.93 3.93 3.94 3.95 3.97 4.04 4.04 4.05 4.06 4.07
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT. KW VALUES ARE FOR THE SYSTEM (OUTDOOR + INDOOR).
Green shaded cells are ACCA (TVA) conditions.
Blue shaded cells are AHRI conditions.