5545023-YTG-G-1121
174 Johnson Controls Ducted Systems
PERFORMANCE DATA - 5 TON
CONDENSER-ONLY DATA (OUTDOOR UNIT)
MODEL
SATURATED SUCTION
AT COMPRESSOR
Outdoor Ambient Temperature
55 °F 65 °F 75 °F 85 °F 95 °F 105 °F 115 °F 125 °F
T (°F) P (PSIG) MBH KW MBH KW MBH KW MBH KW MBH KW MBH KW MBH KW MBH KW
YFK60B21S
(Stage 2)
35 107 55.1 3.06 52.4 3.33 49.8 3.65 47.0 4.02 44.0 4.44 41.0 4.94 37.7 5.52 34.1 6.18
40 118 60.4 3.09 57.6 3.36 54.7 3.67 51.7 4.03 48.6 4.44 45.2 4.94 41.7 5.51 37.9 6.16
45 130 65.9 3.14 63.1 3.40 60.0 3.70 56.7 4.04 53.3 4.45 49.8 4.94 45.9 5.51 41.9 6.14
50 142 71.8 3.20 68.4 3.46 64.8 3.76 61.6 4.08 58.4 4.48 54.6 4.95 50.5 5.51 46.1 6.13
55 156 77.0 3.27 74.5 3.51 70.8 3.81 67.3 4.13 63.6 4.51 59.6 4.98 55.3 5.53 50.7 6.12
YFK60B21S
(Stage 1)
35 107 35.9 2.07 33.9 2.36 32.0 2.68 30.1 3.02 27.9 3.42 25.3 3.89 22.4 4.41 19.2 5.02
40 118 39.7 2.01 37.5 2.31 35.5 2.62 33.4 2.97 31.1 3.36 28.4 3.82 25.4 4.35 22.1 4.94
45 130 43.7 1.96 41.4 2.25 39.2 2.57 36.9 2.92 34.4 3.31 31.7 3.76 28.6 4.28 25.1 4.87
50 142 48.2 1.93 45.6 2.21 43.1 2.52 40.6 2.86 38.0 3.24 35.1 3.69 31.9 4.21 28.2 4.78
55 156 52.8 1.86 49.9 2.15 47.3 2.46 44.6 2.79 41.8 3.17 38.8 3.62 35.4 4.13 31.6 4.70
Notes:
1. For Outdoor Unit (Condenser) performance only. Data does not include the effects of air handler power or heat.
2. Performance based on 15°F subcooling and 15°F superheat at the Outdoor Unit base valves.
a. Increase capacity by 1% for each 2°F increase in subcooling.
b. Decrease capacity by 1% for each 2°F decrease in subcooling.
3. Maximum recommended condensing temperature is 140°F.
COOLING PERFORMANCE DATA
OUTDOOR UNIT MODEL NO. YFK60B21S
INDOOR COIL MODEL NO. CF64DXA1
AIR TEMPERATURE
ENTERING
OUTDOOR UNIT (°F)
ID CFM 1500 1750 2000
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
55
T.C. 55.6 59.6 59.4 61.6 62.0 57.6 60.4 60.2 61.9 62.2 59.6 61.2 61.1 62.1 62.3
S.C. 54.2 46.9 40.5 37.7 29.2 56.5 48.5 41.8 38.5 29.5 58.7 50.2 43.1 39.3 29.9
KW 3.11 3.13 3.13 3.14 3.14 3.21 3.23 3.23 3.23 3.23 3.31 3.32 3.32 3.32 3.32
65
T.C. 54.0 58.0 57.8 61.5 64.5 56.1 59.1 58.9 62.2 65.2 58.2 60.3 60.1 62.9 65.9
S.C. 52.9 46.6 39.8 38.3 30.1 55.1 49.1 41.8 39.9 30.9 57.3 51.6 43.8 41.5 31.7
KW 3.41 3.45 3.45 3.47 3.49 3.52 3.55 3.55 3.57 3.59 3.63 3.65 3.65 3.67 3.68
75
T.C. 52.5 56.4 56.2 61.4 66.9 54.6 57.8 57.6 62.6 68.2 56.8 59.3 59.0 63.8 69.4
S.C. 51.6 46.2 39.1 38.8 31.1 53.7 49.7 41.8 41.2 32.3 55.9 53.1 44.4 43.6 33.5
KW 3.72 3.76 3.76 3.81 3.84 3.83 3.87 3.87 3.91 3.95 3.94 3.98 3.97 4.01 4.05
85
T.C. 51.2 54.4 54.2 59.2 64.2 53.4 55.8 55.6 60.3 65.5 55.6 57.2 56.9 61.4 66.8
S.C. 50.4 45.7 38.6 38.1 30.2 52.6 49.2 41.3 40.6 31.6 54.7 52.8 44.0 43.1 33.0
KW 4.14 4.18 4.18 4.22 4.26 4.25 4.28 4.28 4.32 4.37 4.36 4.39 4.38 4.43 4.47
95
T.C. 50.0 52.4 52.2 57.0 61.5 52.2 53.8
53.5 58.0 62.9 54.4 55.2 54.8 59.0 64.3
S.C. 49.2 45.2 38.0 37.4 29.3 51.4 48.8 40.8 40.0 31.0 53.6 52.4 43.6 42.6 32.6
KW 4.55 4.59 4.59 4.63 4.68 4.66 4.69 4.69 4.73 4.79 4.77 4.80 4.79 4.84 4.90
105
T.C. 46.7 48.7 48.6 53.2 58.1 48.9 50.1 49.7 54.2 59.1 51.1 51.6 50.9 55.2 60.1
S.C. 46.0 43.3 36.2 35.9 28.1 48.1 46.4 39.0 38.5 29.7 50.3 49.5 41.7 41.1 31.3
KW 5.16 5.19 5.19 5.24 5.28 5.27 5.30 5.29 5.34 5.39 5.38 5.40 5.40 5.45 5.50
115
T.C. 43.5 45.1 45.1 49.6 54.8 45.7 46.6 46.1 50.5 55.4 47.8 48.1 47.1 51.5 56.0
S.C. 42.9 41.4 34.6 34.4 26.9 45.0 44.1 37.2 37.0 28.5 47.1 46.7 39.8 39.6 30.0
KW 5.75 5.77 5.77 5.83 5.87 5.87 5.88 5.88 5.93 5.97 5.98 5.99 5.99 6.04 6.08
125
T.C. 40.4 41.5 41.6 46.0 51.6 42.5 43.1 42.4 46.8 51.8 44.6 44.7 43.3 47.7 51.9
S.C. 39.7 39.5 32.9 32.9 25.8 41.8 41.7 35.4 35.5 27.2 43.9 44.0 37.9 38.2 28.7
KW 6.35 6.36 6.35 6.42 6.45 6.46 6.47 6.47 6.52 6.56 6.57 6.58 6.58 6.63 6.66
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT. KW VALUES ARE FOR THE SYSTEM (OUTDOOR + INDOOR).
Green shaded cells are ACCA (TVA) conditions.
Blue shaded cells are AHRI conditions.