SM-18001
SERVICE MANUAL
INVERTER-DRIVEN MULTI-SPLIT SYSTEM
HEAT PUMP AIR CONDITIONERS
Service Manual
< Indoor Units >
●Ducted(HighStatic)Type
(H,Y)IDH018B21S
(H,Y)IDH024B21S
(H,Y)IDH030B21S
(H,Y)IDH036B21S
(H,Y)IDH048B21S
●Ducted(MediumStatic)Type
(H,Y,C)IDM006B21S
(H,Y,C)IDM008B21S
(H,Y,C)IDM012B21S
(H,Y,C)IDM015B21S
(H,Y,C)IDM018B21S
(H,Y,C)IDM024B21S
(H,Y,C)IDM030B21S
(H,Y,C)IDM036B21S
(H,Y,C)IDM048B21S
●Ducted(Slim)Type
(H,Y,C)IDS006B21S
(H,Y,C)IDS008B21S
(H,Y,C)IDS012B21S
(H,Y,C)IDS015B21S
(H,Y,C)IDS018B21S

Table of Contents

Questions and Answers

Summary

SERVICE MANUAL

INVERTER-DRIVEN MULTI-SPLIT SYSTEM HEAT PUMP AIR CONDITIONERS

Specifies the system type covered in the manual.

2. Important Safety Instructions

General Precautions

Lists general precautions to reduce the risk of serious injury or death during installation and use.

Installation Precautions

Refrigerant Precautions

Electrical Precautions

1. Installation

2. Operation

3. Troubleshooting

3.1 Initial Troubleshooting

Covers initial troubleshooting steps, focusing on electrical wiring and power supply checks.

3.1.1 Checking Electrical Wiring and Power Supply

Details checks for power supply breakers, transformer voltage, and wiring connections.

3.1.3 Checking Rotary Switch and DIP Switch Settings

3.1.4 Checking Wired Controller

Alarm History Display Procedure

I.U.;O.U. PCB Check Procedure

Wired Controller Self-Checking Functions

3.2 Troubleshooting Procedures

Alarm Code Indication on Wired Controller

Explains how alarm codes are indicated on the wired controller and the change-over box PCB.

3.2.1 Alarm Code Table

3.2.2 Troubleshooting Using Alarm Codes

Troubleshooting Flowchart: Float Switch & Condensate Pump

Troubleshooting Flowchart: Alarm Code 03 Communication Failure

PCB & Change-Over Box Troubleshooting Flowcharts

Troubleshooting Flowcharts: Power & Circuit Issues

Alarm Code 11: Inlet Air Thermistor Abnormality

Alarm Code 12: Outlet Air Thermistor Abnormality

Alarm Code 13: Liquid Pipe Thermistor Abnormality

Alarm Code 14: Gas Pipe Thermistor Abnormality

Alarm Code 19: Indoor Fan Motor Protection Device

Alarm Code 31: Incorrect Capacity Setting

Alarm Code 35: Incorrect Indoor Unit Number Setting

Incorrect Unit Model Code and Unit;Refrigerant Cycle Settings

Alarm Code b0: Unit Model Code Setting Error

Troubleshooting guide for alarm code "b0" related to incorrect unit model code settings.

Alarm Code b1: Unit and Refrigerant Cycle Number Setting Error

Troubleshooting guide for alarm code "b1" related to incorrect unit or refrigerant cycle number settings.

3.2.3 Abnormalities of Devices

Device Abnormalities: Other Settings

Incorrect Optional Settings

Details issues related to incorrect optional settings on the wired controller.

Incorrect Input;Output Settings

Addresses abnormalities arising from incorrect input/output configurations.

Device Abnormalities: Fan Speed, Defrost, and Controller Indicators

Indoor Fan Speed Not Changed

Troubleshooting for situations where the indoor fan speed does not change.

Defrost Operation and Controller Indicator Issues

Covers issues when defrosting operation is not available and controller indicators remain lit.

Device Abnormalities: Insufficient Cooling - Pressure, Airflow, Sensor

Low Suction Pressure Issues

Discusses problems related to excessively low suction pressure during cooling.

Indoor Airflow and Motion Sensor Control

Addresses insufficient airflow to the indoor unit heat exchanger and motion sensor control issues.

Device Abnormalities: Cooling Operation - Pressure & Valve Issues

Valve Malfunctions and Suction Pressure

Covers reversing valve and suction pressure related malfunctions.

Device Abnormalities: Cooling Operation - Communication & PCB Issues

Communication Failure and PCB Failures

Troubleshooting for communication failure and indoor unit PCB issues.

Insufficient Power Supply & EconoFresh Kit Issues

Covers insufficient power supply and EconoFresh Kit related problems.

Device Abnormalities: Heating Operation - Airflow, Temperature & Valve Issues

Airflow, Temperature, and Refrigerant Issues

Addresses problems with airflow, temperature, and refrigerant during heating operation.

Valve Malfunctions and Heat Exchanger Issues

Covers reversing valve and outdoor unit heat exchanger related malfunctions.

Device Abnormalities: Heating Operation - Communication & Power Issues

Device Abnormalities: Heating Operation - Pressure & Valve Issues

High Discharge Pressure & Refrigerant Issues

Discusses high discharge pressure and refrigerant-related problems.

Valve Malfunctions and Suction Pressure Issues

Covers reversing valve and suction pressure related malfunctions.

Check Valve & Expansion Valve Issues

Addresses problems with check valves and expansion valves.

Device Abnormalities: Sound & Fan Operation Issues

Abnormal Sounds and Fan Motor Issues

Troubleshooting for abnormal sounds and fan motor issues during operation.

Outdoor Fan & Compressor Problems

Covers outdoor fan issues and compressor problems like abnormal sound or heat.

Indoor Fan & AC Chopper Issues

Addresses indoor fan operation and AC chopper related problems.

Device Abnormalities: Motion and Radiation Sensor Operation

Motion Sensor Activation and Operation Status Issues

Troubleshooting for motion sensor activation and operation status discrepancies.

Sensor Sensitivity and No Presence Settings

Covers sensor sensitivity adjustments and no presence setting issues.

Radiation Sensor Activation Issues

Addresses radiation sensor activation and potential abnormalities.

Device Abnormalities: Motion and Radiation Sensor Heating Operation

Heating Radiation Sensor Operation Issues

Troubleshooting for heating radiation sensor operation when the room is already heated.

No Heating Radiation Sensor Operation

Covers issues when the heating radiation sensor does not operate in a cold room.

Motion Sensor Setting and Communication Errors

Addresses problems with motion sensor settings and communication errors.

3.3 Procedures for Checking

3.4 Test Run

Test Run Using Wired Controller

3.4.3 Checking the Test Run

4. Maintenance

4.2 Maintenance of Indoor Unit

4.2.1.3 Removing Fan and Fan Motor

B. Removing Fan and Fan Motor from Bottom Side (For All Models)

4.2.2 Ducted Medium Static Type ((H,Y,C)IDM006 - 048 B21 S)

4.2.2.3 Removing Fan and Fan Motor

4.2.3 Ducted Slim Type ((H,Y,C)IDS006 - 018 B21 S)

4.2.3.3 Removing Fan and Fan Motor from Bottom Side (For All Models)

4.3 Cleaning Indoor Unit Heat Exchanger

4.3.2 Cleaning Procedure

Cleaning with Clean Water

4.4.3 for Indoor Units

Printed Circuit Boards for Ducted Medium Static Units

Printed Circuit Boards for Ducted Slim Units

4.4.3.2 Fan Motor (Ducted High Static)

Fan Motor Details for Ducted Medium Static Units

Fan Motor Details for Ducted Medium Static (Model: (H,Y,C)IDM024 - 048 B21 S)

Fan Motor Details for Ducted Slim (Model: (H,Y,C)IDS006 - 012 B21 S)

Fan Motor Details for Ducted Slim (Model: (H,Y,C)IDS015,018 B21 S)

4.4.3.3 Thermistor Positions

4.4.3.4 Electronic Expansion Valve

5. External Input;Output and Function Setting

5.4 External Input;Output and Function Setting Mode for Indoor Unit

Function Selection and Input;Output Setting via Wired Controller

5.4.1 External Input and Output Settings

5.4.1.1 Remote Control ON;OFF Function (Level Signal)

Remote ON;OFF Functions - Pulse Signals

(2) Remote ON;OFF 2 (Pulse Signal Input)

Details the remote ON/OFF function using pulse signals, including wiring and time charts.

(3) Remote ON;OFF 3 (Pulse Signal Input)

Explains the remote ON/OFF function using pulse signals for stopping units.

Remote Control Stoppage Function (Pulse Signal)

Forbidding Remote Control after Manual Stoppage

Power Supply ON;OFF Functions

5.4.1.2 Power Supply ON;OFF 1 (Automatic Operation)

Explains automatic unit operation based on power supply status.

5.4.1.3 Power Supply ON;OFF 2 (Restarting After Power Failure)

Details the automatic unit restarting function after a power failure.

Control by Field-Supplied Room Thermostat

5.4.1.5 Remote Cooling;Heating Change

5.4.1.6 Picking Up Operation Signal

5.4.2 Function Setting

5.4.2.1 Function Selection Item

Lists and describes various optional functions and their setting conditions.

Optional Function Selection Items (Part 1)

Optional Function Selection Items (Part 2)

Optional Function Selection Items (Part 3)

Optional Function Selection Items (Part 4)

Optional Function Selection Items (Part 5)

Specific Function Descriptions: Thermistor, Stoppage Logic, Louver Angle, Power ON;OFF

Power Supply ON;OFF (d1)

Explains automatic operation based on power supply status.

Specific Function Descriptions: Power ON;OFF, Temperature Decrease Prevention

Power Supply ON;OFF 2 (Restarting) (d3)

Details the automatic unit restarting function after a power failure.

5.5 Functions from Wired Controller

5.5.1 Power Saving Function

Explains the power saving function, including Peak Cut and Moderate Control.

5.5.2 Schedule Function

5.5.3 Indication Function

5.5.4 Comfort Function

6. Field Work Instructions

6.1 Caution for Refrigerant Leakage

Provides special attention regarding refrigerant gas leakage and safety standards like ASHRAE 15.

6.2 Modifications of Charging Refrigerants Other than Those Specified by Johnson Controls

6.3 Maintenance Work

6.5 Service and Maintenance Record by Wired Controller

6.6 Service and Maintenance Record Checklist

Summary

SERVICE MANUAL

INVERTER-DRIVEN MULTI-SPLIT SYSTEM HEAT PUMP AIR CONDITIONERS

Specifies the system type covered in the manual.

2. Important Safety Instructions

General Precautions

Lists general precautions to reduce the risk of serious injury or death during installation and use.

Installation Precautions

Refrigerant Precautions

Electrical Precautions

1. Installation

2. Operation

3. Troubleshooting

3.1 Initial Troubleshooting

Covers initial troubleshooting steps, focusing on electrical wiring and power supply checks.

3.1.1 Checking Electrical Wiring and Power Supply

Details checks for power supply breakers, transformer voltage, and wiring connections.

3.1.3 Checking Rotary Switch and DIP Switch Settings

3.1.4 Checking Wired Controller

Alarm History Display Procedure

I.U.;O.U. PCB Check Procedure

Wired Controller Self-Checking Functions

3.2 Troubleshooting Procedures

Alarm Code Indication on Wired Controller

Explains how alarm codes are indicated on the wired controller and the change-over box PCB.

3.2.1 Alarm Code Table

3.2.2 Troubleshooting Using Alarm Codes

Troubleshooting Flowchart: Float Switch & Condensate Pump

Troubleshooting Flowchart: Alarm Code 03 Communication Failure

PCB & Change-Over Box Troubleshooting Flowcharts

Troubleshooting Flowcharts: Power & Circuit Issues

Alarm Code 11: Inlet Air Thermistor Abnormality

Alarm Code 12: Outlet Air Thermistor Abnormality

Alarm Code 13: Liquid Pipe Thermistor Abnormality

Alarm Code 14: Gas Pipe Thermistor Abnormality

Alarm Code 19: Indoor Fan Motor Protection Device

Alarm Code 31: Incorrect Capacity Setting

Alarm Code 35: Incorrect Indoor Unit Number Setting

Incorrect Unit Model Code and Unit;Refrigerant Cycle Settings

Alarm Code b0: Unit Model Code Setting Error

Troubleshooting guide for alarm code "b0" related to incorrect unit model code settings.

Alarm Code b1: Unit and Refrigerant Cycle Number Setting Error

Troubleshooting guide for alarm code "b1" related to incorrect unit or refrigerant cycle number settings.

3.2.3 Abnormalities of Devices

Device Abnormalities: Other Settings

Incorrect Optional Settings

Details issues related to incorrect optional settings on the wired controller.

Incorrect Input;Output Settings

Addresses abnormalities arising from incorrect input/output configurations.

Device Abnormalities: Fan Speed, Defrost, and Controller Indicators

Indoor Fan Speed Not Changed

Troubleshooting for situations where the indoor fan speed does not change.

Defrost Operation and Controller Indicator Issues

Covers issues when defrosting operation is not available and controller indicators remain lit.

Device Abnormalities: Insufficient Cooling - Pressure, Airflow, Sensor

Low Suction Pressure Issues

Discusses problems related to excessively low suction pressure during cooling.

Indoor Airflow and Motion Sensor Control

Addresses insufficient airflow to the indoor unit heat exchanger and motion sensor control issues.

Device Abnormalities: Cooling Operation - Pressure & Valve Issues

Valve Malfunctions and Suction Pressure

Covers reversing valve and suction pressure related malfunctions.

Device Abnormalities: Cooling Operation - Communication & PCB Issues

Communication Failure and PCB Failures

Troubleshooting for communication failure and indoor unit PCB issues.

Insufficient Power Supply & EconoFresh Kit Issues

Covers insufficient power supply and EconoFresh Kit related problems.

Device Abnormalities: Heating Operation - Airflow, Temperature & Valve Issues

Airflow, Temperature, and Refrigerant Issues

Addresses problems with airflow, temperature, and refrigerant during heating operation.

Valve Malfunctions and Heat Exchanger Issues

Covers reversing valve and outdoor unit heat exchanger related malfunctions.

Device Abnormalities: Heating Operation - Communication & Power Issues

Device Abnormalities: Heating Operation - Pressure & Valve Issues

High Discharge Pressure & Refrigerant Issues

Discusses high discharge pressure and refrigerant-related problems.

Valve Malfunctions and Suction Pressure Issues

Covers reversing valve and suction pressure related malfunctions.

Check Valve & Expansion Valve Issues

Addresses problems with check valves and expansion valves.

Device Abnormalities: Sound & Fan Operation Issues

Abnormal Sounds and Fan Motor Issues

Troubleshooting for abnormal sounds and fan motor issues during operation.

Outdoor Fan & Compressor Problems

Covers outdoor fan issues and compressor problems like abnormal sound or heat.

Indoor Fan & AC Chopper Issues

Addresses indoor fan operation and AC chopper related problems.

Device Abnormalities: Motion and Radiation Sensor Operation

Motion Sensor Activation and Operation Status Issues

Troubleshooting for motion sensor activation and operation status discrepancies.

Sensor Sensitivity and No Presence Settings

Covers sensor sensitivity adjustments and no presence setting issues.

Radiation Sensor Activation Issues

Addresses radiation sensor activation and potential abnormalities.

Device Abnormalities: Motion and Radiation Sensor Heating Operation

Heating Radiation Sensor Operation Issues

Troubleshooting for heating radiation sensor operation when the room is already heated.

No Heating Radiation Sensor Operation

Covers issues when the heating radiation sensor does not operate in a cold room.

Motion Sensor Setting and Communication Errors

Addresses problems with motion sensor settings and communication errors.

3.3 Procedures for Checking

3.4 Test Run

Test Run Using Wired Controller

3.4.3 Checking the Test Run

4. Maintenance

4.2 Maintenance of Indoor Unit

4.2.1.3 Removing Fan and Fan Motor

B. Removing Fan and Fan Motor from Bottom Side (For All Models)

4.2.2 Ducted Medium Static Type ((H,Y,C)IDM006 - 048 B21 S)

4.2.2.3 Removing Fan and Fan Motor

4.2.3 Ducted Slim Type ((H,Y,C)IDS006 - 018 B21 S)

4.2.3.3 Removing Fan and Fan Motor from Bottom Side (For All Models)

4.3 Cleaning Indoor Unit Heat Exchanger

4.3.2 Cleaning Procedure

Cleaning with Clean Water

4.4.3 for Indoor Units

Printed Circuit Boards for Ducted Medium Static Units

Printed Circuit Boards for Ducted Slim Units

4.4.3.2 Fan Motor (Ducted High Static)

Fan Motor Details for Ducted Medium Static Units

Fan Motor Details for Ducted Medium Static (Model: (H,Y,C)IDM024 - 048 B21 S)

Fan Motor Details for Ducted Slim (Model: (H,Y,C)IDS006 - 012 B21 S)

Fan Motor Details for Ducted Slim (Model: (H,Y,C)IDS015,018 B21 S)

4.4.3.3 Thermistor Positions

4.4.3.4 Electronic Expansion Valve

5. External Input;Output and Function Setting

5.4 External Input;Output and Function Setting Mode for Indoor Unit

Function Selection and Input;Output Setting via Wired Controller

5.4.1 External Input and Output Settings

5.4.1.1 Remote Control ON;OFF Function (Level Signal)

Remote ON;OFF Functions - Pulse Signals

(2) Remote ON;OFF 2 (Pulse Signal Input)

Details the remote ON/OFF function using pulse signals, including wiring and time charts.

(3) Remote ON;OFF 3 (Pulse Signal Input)

Explains the remote ON/OFF function using pulse signals for stopping units.

Remote Control Stoppage Function (Pulse Signal)

Forbidding Remote Control after Manual Stoppage

Power Supply ON;OFF Functions

5.4.1.2 Power Supply ON;OFF 1 (Automatic Operation)

Explains automatic unit operation based on power supply status.

5.4.1.3 Power Supply ON;OFF 2 (Restarting After Power Failure)

Details the automatic unit restarting function after a power failure.

Control by Field-Supplied Room Thermostat

5.4.1.5 Remote Cooling;Heating Change

5.4.1.6 Picking Up Operation Signal

5.4.2 Function Setting

5.4.2.1 Function Selection Item

Lists and describes various optional functions and their setting conditions.

Optional Function Selection Items (Part 1)

Optional Function Selection Items (Part 2)

Optional Function Selection Items (Part 3)

Optional Function Selection Items (Part 4)

Optional Function Selection Items (Part 5)

Specific Function Descriptions: Thermistor, Stoppage Logic, Louver Angle, Power ON;OFF

Power Supply ON;OFF (d1)

Explains automatic operation based on power supply status.

Specific Function Descriptions: Power ON;OFF, Temperature Decrease Prevention

Power Supply ON;OFF 2 (Restarting) (d3)

Details the automatic unit restarting function after a power failure.

5.5 Functions from Wired Controller

5.5.1 Power Saving Function

Explains the power saving function, including Peak Cut and Moderate Control.

5.5.2 Schedule Function

5.5.3 Indication Function

5.5.4 Comfort Function

6. Field Work Instructions

6.1 Caution for Refrigerant Leakage

Provides special attention regarding refrigerant gas leakage and safety standards like ASHRAE 15.

6.2 Modifications of Charging Refrigerants Other than Those Specified by Johnson Controls

6.3 Maintenance Work

6.5 Service and Maintenance Record by Wired Controller

6.6 Service and Maintenance Record Checklist

York YIDH048B21S Specifications

General IconGeneral
Model NumberYIDH048B21S
CategoryAir Conditioner
Cooling Capacity48000 BTU/h
EER11.5
Power Supply208-230V/60Hz/1Ph
RefrigerantR-410A