JOHNSON CONTROLS
FORM 100.50-SU3 (1207)
ADDRESS
NUMBER
DESCRIPTION UNITS OF ADJUSTMENT
RANGE OF
ADJUSTMENT
CURRENT
SETTING
72/73/74/
75/76
ALARM ARRAY DATA - 5 CHARACTERS 0 - 255 0
77 VAV / CV SELECTION READ ONLY FLAG
CV = 0
VAV = 1
0
78 HOT GAS REHEAT PARAMETER BIT 0 = OFF, 1 = ON OFF
79 HOT GAS PRESENT ON COMPRESSOR # 1 PARAMETER BIT 0 = OFF, 1 = ON OFF
80 COMPRESSORS AVAILABLE FOR COOLING PARAMETER BIT 2 - 4 2
81 STAGES OF HEAT AVAILABLE PARAMETER BIT
0 - 3
0 = DISABLED
2
82 DUCT STATIC READING
PRESSURE - INCHES OF
H2O
0.000 - 5.000 0000
83 BUILDING STATIC PRESSURE
PRESSURE - INCHES OF
H2O
0.000 - 5.000 0000
84 LOW AMBIENT KIT INSTALLED PARAMETER BIT 0 = OFF, 1 = ON OFF
85 BUILDING STATIC PRESSURE SENSOR INSTALLED PARAMETER BIT 0 = OFF, 1 = ON OFF
86 ERV INSTALLED PARAMETER BIT 0 = OFF, 1 = ON OFF
87 ERV UNOCCUPIED FAN ENABLE PARAMETER BIT 0 = OFF, 1 = ON OFF
88 DUCT STATIC SHUTDOWN SETPOINT
PRESSURE - INCHES OF
H2O
0.000 - 5.000 4.500
TABLE - 6-1 - PARAMETER POINTS LIST (CONT.)