1061903-XIM-A-0713
28 Johnson Controls Unitary Products
Table 19: Air Flow Performance - Side Duct Application
ZF180-240 Side Duct Application
ZF180 (15 Ton) Side Duct Imperial
Air Flow
(CFM)
Available External Static Pressure - IWG
1
0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
High Static 4.0 HP & Field Supplied Drive High Static 4.0 HP & OEM Supplied Drive
4400 760 1.56 798 1.90 835 2.20 878 2.47 950 2.81 1014 3.11 1069 3.38 1115 3.61 1154 3.81 1184 3.97 1205 4.09 1218 4.18
4800 786 1.93 824 2.27 861 2.57 904 2.84 976 3.18 1040 3.48 1095 3.75 1142 3.98 1180 4.18 1210 4.34 1231 4.46 1244 4.55
5200 815 2.34 853 2.68 890 2.98 933 3.25 1005 3.59 1068 3.89 1123 4.16 1170 4.39 1208 4.59 1238 4.75 1260 4.87 1273 4.96
5600 845 2.79 883 3.13 920 3.43 963 3.70 1035 4.04 1099 4.34 1154 4.61 1200 4.84 1239 5.04 1269 5.20 1290 5.32 1303 5.41
6000 877 3.28 915 3.62 952 3.92 995 4.19 1067 4.53 1131 4.83 1186 5.10 1232 5.33 1271 5.53 - - ----
6400 911 3.81 949 4.15 986 4.45 1029 4.72 1101 5.06 1164 5.36 1219 5.63 ----------
6800 946 4.38 984 4.72 1021 5.02 1064 5.29 - - --------------
7200 982 4.98 1020 5.32 1057 5.62 ------------------
Field Supplied Motor & Drive
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.838.
ZF180 (15 Ton) Side Duct Metric
Air Flow
M
3
/sec.
Available External Static Pressure - Pa
1
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
100 149 199 249 299 349 399 448 498 548 598 648
RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM Kw RPM kW
High Static 4.0 HP & Field Supplied Drive High Static 4.0 HP & OEM Drive
2.08 760 1.16 798 1.42 835 1.64 878 1.84 950 2.09 1014 2.32 1069 2.52 1115 2.69 1154 2.84 1184 2.96 1205 3.50 1218 3.12
2.27 786 1.44 824 1.69 861 1.92 904 2.12 976 2.37 1040 2.60 1095 2.80 1142 2.97 1180 3.12 1210 3.24 1231 3.33 1244 2.39
2.45 815 1.75 853 2.00 890 2.22 933 2.42 1005 2.68 1068 2.90 1123 3.10 1170 3.27 1208 3.42 1238 3.54 1260 3.63 1273 3.70
2.64 845 2.08 883 2.33 920 2.56 963 2.76 1035 3.01 1099 3.24 1154 3.44 1200 3.61 1239 3.76 1269 3.88 1290 3.97 1303 4.03
2.83 877 2.45 915 2.70 952 2.92 995 3.12 1067 3.38 1131 3.60 1186 3.80 1232 3.97 1271 4.12 - - - - - -
3.02 911 2.84 949 3.10 986 3.32 1029 3.52 1101 3.77 1164 4.00 1219 4.20 - - - - - - - - - -
3.21 946 3.27 984 3.52 1021 3.74 1064 3.94 - - - - - - - - - - - - - - - -
3.40 982 3.71 1020 3.97 1057 4.19 - - - - - - - - - - - - - - - - - -
Field Supplied Motor & Drive

Table of Contents