5167515-YIM-H-0518
Johnson Controls Ducted Systems 53
Operation
Cooling Sequence Of Operation
NOTE: For more in-depth sequence of operation of the Smart
Equipment™ control, refer to the Smart Equipment™
Controls Sequence of Operation Overview LIT-
12011950 available from your equipment dealer or
distributor.
For ZH units, a "Y1" call for the first stage of cooling is passed
to the Unit Control Board (UCB) which then determines whether
the requested operation is available and if so, which
components to energize. With a "Y1" call for first stage cooling
the UCB will determine if a first stage cooling output is valid as
long as all safeties and time-delays allow a C1 output for
cooling. The C1 relay on the UCB will close and send 24 volts
to the M1 contactor starting the first stage compressor and also
energizing M4 contactor starting the associated condenser
fans. During any call for fan or cooling the FAN output on the
UCB will energize the M3 contactor starting the supply fan.
NOTE: If a Y2 call is present it is passed to the Unit Control
Board (UCB) which then determines whether the
requested operation is available and if so, which
components to energize. With a "Y2" call for first stage
Table 23: Additional Static Resistance
Size
(Tons)
Model CFM Cooling Only
1
1. Add these values to the available static resistance in the respective Blower Performance Tables.
Economizer
2
,
3
2. Deduct these values from the available external static pressure shown in the respective Blower Performance Tables.
3. The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct is
less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.
4” Filter
2
Electric Heat kW
2
9 18243654
078 (6.5)
090 (7.5)
ZH
1900 0.00 0.07 0.10 0.05 0.06 0.07 0.08 0.10
2100 -0.01 0.09 0.11 0.06 0.07 0.08 0.09 0.11
2300 -0.01 0.11 0.12 0.07 0.08 0.09 0.10 0.13
2500 -0.02 0.13 0.14 0.08 0.09 0.10 0.11 0.14
2700 -0.03 0.16 0.15 0.09 0.10 0.12 0.13 0.16
2900 -0.04 0.18 0.16 0.10 0.11 0.13 0.14 0.18
3100 -0.05 0.20 0.18 0.12 0.13 0.15 0.16 0.20
3300 -0.06 0.22 0.19 0.13 0.14 0.17 0.18 0.22
3500 -0.07 0.24 0.20 0.15 0.16 0.19 0.20 0.24
3700 -0.08 0.27 0.21 0.17 0.18 0.21 0.22 0.26
3900 -0.09 0.29 0.23 0.19 0.20 0.23 0.24 0.28
4100 -0.09 0.31 0.24 0.21 0.22 0.25 0.26 0.31
4300 -0.10 0.30 0.25 0.23 0.24 0.28 0.29 0.34
4500 -0.11 0.35 0.26 0.25 0.26 0.30 0.31 0.37
102 (8.5)
120 (10)
150 (12.5)
ZH
1900 0.06 0.02 0.12 0.05 0.06 0.07 0.08 0.10
2100 0.07 0.02 0.13 0.06 0.07 0.08 0.09 0.11
2300 0.08 0.04 0.14 0.07 0.08 0.09 0.10 0.13
2500 0.09 0.11 0.16 0.08 0.09 0.10 0.11 0.14
2700 0.11 0.18 0.17 0.09 0.10 0.12 0.13 0.16
2900 0.12 0.25 0.19 0.10 0.11 0.13 0.14 0.18
3100 0.14 0.31 0.20 0.12 0.13 0.15 0.16 0.20
3300 0.16 0.37 0.22 0.13 0.14 0.17 0.18 0.22
3500 0.18 0.43 0.26 0.15 0.16 0.19 0.20 0.24
3700 0.20 0.49 0.27 0.17 0.18 0.21 0.22 0.26
3900 0.23 0.54 0.29 0.19 0.20 0.23 0.24 0.28
4100 0.25 0.58 0.32 0.21 0.22 0.25 0.26 0.31
4300 0.28 0.65 0.35 0.23 0.24 0.28 0.29 0.34
4500 0.30 0.69 0.38 0.25 0.26 0.30 0.31 0.37
4700 0.33 0.74 0.41 0.28 0.29 0.33 0.34 0.40
4900 0.36 0.78 0.44 0.30 0.31 0.35 0.37 0.43
5100 0.39 0.82 0.47 0.33 0.34 0.38 0.40 0.46
5300 0.42 0.86 0.51 0.35 0.37 0.41 0.43 0.49
5500 0.45 0.89 0.55 0.38 0.40 0.44 0.46 0.53
5700 0.48 0.93 0.58 0.41 0.43 0.47 0.49 0.56
5900 0.52 0.96 0.62 0.44 0.46 0.50 0.53 0.59
6100 0.56 0.98 0.67 0.47 0.49 0.53 0.56 0.62
6300 0.60 1.01 0.71 0.50 0.53 0.56 0.59 0.65