EasyManua.ls Logo

Yudian AI-208 - Parameter and Setting; Field Parameter Table; System Parameter Table

Yudian AI-208
7 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Yudian (H.K.) Automation Technology Co. Ltd.
Website: http://www.yudian.us
http://www.yudian.com.hk
Email: sales@yudian.com.hk
Tel: +852-2770 8785 Fax: +852-2770 8796
V. PARAMETER AND SETTING
Parameter Title Description Range
Field Parameter Table (Press and hold 3 for 2 seconds to access)
HIA
High limit alarm
Alarm on when PV (Process Value) >HIA;
alarm off when PV<HIA-AHY
0999
LoA
Lower limit alarm
Alarm on when PV (Process Value) < LoA;
alarm off when PV > LoA+AHY
0999
HdA
Deviation high
alarm
Alarm on when PV-SV>HdA;
alarm off when PV-SV<HdA-AHY
0999
LdA
Deviation low
alarm
Alarm on when PV-SV<LdA;
alarm off when PV-SV>LdA+AHY
0999
Loc Parameter lock
Loc=0: Allowed to change HIA, LoA, HdA, LdA and SV.
Loc=1: Allowed to read only HIA, LoA, HdA, LdA but to change SV.
Loc=2~3: Allowed to change HIA, LoA, HdA. LdA but read only SV.
Loc=4~255: NOT allowed to change any parameters nor SV.
Loc=808, Set to 808 and press 3 to unlock the System Parameter Table.
0255
System Parameter Table (Loc=808 to unlock)
AHY
Alarm Hysteresis
Avoid frequent alarm on-off action because of the fluctuation of PV
AHY=2 by default.
0~200
AOP
Alarm output
assignment
HdA &
(x100)
LdA
LoA
(x10)
HIA
(x1)
0 ± ± 0 ± 0 ±
1 AU1 ± 1AU1 1 AU1
2 AU2 ± 2AU2 2 AU2
5
A
U1
A
U1
6 AU2 AU1
7 ±
A
U1
8 ±
A
U
2
9
A
U1
A
U
2
Example: AOP=901 refers to HdA assigned to AU1, LdA to AU2,
without LoA and HIA to AU1.
0~922
CrL Control mode
z onF : ON-OFF control. When PV>SV, output stops and heating
stops. When PV<SV-AHY, output resumes.
z AI : AI-PID control. The output time proportion can adjusted by
parameter Ctl
Act Acting method
rE: Reverse acting. Increase in measured variable causes a decrease
in the output, such as heating control.
dr: Direct acting. Increase in measured variable causes an increase in
the output, such as refrigerating control.
rEb: Reverse acting with low limit alarm and deviation low alarm
blocking at the beginning of power on.
drb: Direct acting with high limit alarm and deviation high alarm
blocking at the beginning of power on.
rE , dr ,
rEb, drb
P Proportion band
Proportion band in PID with unit or but not the percentage of the
input scale.
1~999
I Time of integral Time of integral in PID. No integral effect when I=0 0~999 sec
d
Time of
derivative
Time of derivative in PID with unit 0.1 second. No derivative effect
when d=0
0~999 sec

Other manuals for Yudian AI-208

Related product manuals