Ctl Control period
Smaller value will result in higher control accuracy.
For SSR output, generally 0.5 to 3 seconds.
For Relay output, generally 15 to 40 seconds, because small value will
cause the frequent On-Off of mechanical switch and shorten its service
life. Ctl is recommended to be 1/4 – 1/10 of derivative time. When
control under on-off control, Ctl is used as delay time to restart to
protect the compressor.
0.5-300 sec
CHY
Control
hysteresis
To avoid frequent relay on-off action, in ON-OFF control mode.
PV > SV, Output turns OFF (Relay opens)
PV < SV-CHY, Output turns ON (Relay closes)
0~200
InP
Input
specification
Thermocouples & RTD
0 K
4 E
5 J
7 N
21 Pt100
021
dPt Resolution 0 or 0.0 selectable. 0.0 is valid for 0~99.9 / display
Scb Input shift
Scb is used to make input shift to compensate the error produced by
sensor or input signal.
PV after compensation= PV before compensation + Scb.
-99+99
FIL PV input filter
Higher degree of FIL gives more powerful noise filtering.
Large FIL value stabilized the input signal but the system response
speed will be slow. Generally speaking, 1 to 3 will be used.
If great interference exists, FIL can be gradually increase to limit the
momentary fluctuation among 2 to 5 unit.
When the instrument is being metrological verified, FIL should be set to
0 or 1 to minimize the response time.
040
Fru
Selection of
power frequency
and temperature
scale
50C: 50Hz,
50F: 50Hz,
60C: 60Hz,
60F: 60Hz,
SPH Upper limit of SV
Maximum value that SV allowed to be.
When SPH=400, the SV range will 0~400
0999