5
SCHx Scale high limit
units
Scbx Input offset
For thermocouple, the units of Scb is 0.1 . For example, when Sc b=-100,
the actual offset=-10 , then the measured temperature will be 10 lower
than that when Sc=0.
-1999~+4000
units or 0.1
FILx Digital filter
The value of FIL will determine the ability of filtering noise.
FIL=0, no filtering;
FIL=1, filtering with mean;
FIL=2~40, filtering with mean and integral.
When a large value is set, the measurement input is stabilized but the
response speed is slow. Generally, it can be set to 1 to 3.
If strong interference exists, then you can increase parameter FIL gradually to
make momentary fluctuation of measured value less than 2 to 5.
When the instrument is being metrological verified, FIL can be set to 0 or 1 to
shorten the response time.
0~40
Px
Proportional
band
Proportional band in PID and APID control. Instead of percentage of the
measurement range, the unit is the same as PV.
Generally, optimal P, I, D and CtI can be obtained by auto tuning. They can
also be manually inputted if you already know the correct values.
109999 units
Ix Time of Integral Time of Integral in PID. No integral effect when I=0
09999
seconds
Dx
Time of
derivative
Time of derivative in PID. No derivative effect when d=0
0999.9
seconds
H.ALx Alarm high limit
x channel high alarm is triggered when PVx (the present value of x
channel)>H.ALx; alarm releases when PVx<H.ALx - HYSx.
-999~+3200
L.ALx Alarm low limit
x channel low alarm is triggered when PVx<L.ALx;
alarm releases when PVx>L.ALx+HYSx.
HYSx Hysteresis
HYS is set to avoid high frequent alarm on/off actions caused by process
input fluctuation. It also works at auto-tuning.
0~999.9
AOPx
Alarm output
allocation
(D5 size not
support this
function)
A
larm
Output to
Low limit alarm High limit alarm
None 0 0
AL1 3 3
AL2 4 4
For example, AOP1=43 that the low limit alarm of channel 1 is sent to AL2,
and high limit alarms sent to AL1
0~44
Cn
Number of
input channels
Define actual number of input channels. Setting range is 1~4.
When Cn=2, the lower window display the present value of channel 2 instead
of the channel number.
1~ 4
Cno
First display
channel setting
If several of AI-7048 has used, this parameter can define the AI-7048 to
display assigned channel number on display. For example, when Cno=6, the
controller will display channel number from 6~9. (6, 7, 8, 9)
AF
Addition
function setting
1
Parameter “AF” was defined as below:
AF=A x 1 + B x 2 + C x 3 + D x 4
A=0; Normal speed in channel cycle display;
A=1; Faster speed in channel cycle display;
B=0; C=0;
D=0; Normal application; D=1; Change all of the low alarm to be high alarm;
AF2
Addition
function setting
2
Parameter “AF2” was defined as below:
AF=A x 1 + B x 2
A=0; Normal application;
A=1; Change all of the high alarm to be high deviation alarm; when deviation
value (PV – SV) > H.ALx, it will trigger the alarm. When (PV SV) < H.ALx
HYSx, alarm off, set the H.ALx value to maximum will disable the alarm
function.