DISABLEMENT AND TEST FUNCTIONS: -
Test Zone –
This feature allows one person to check the detectors
and sounders without having to return to the panel
during the testing routine. When the appropriate zone is
in test mode and a detector is activated, the sounder
circuit/s will operate for a few seconds and then
automatically reset.
Access “SUPERVISOR MODE"
Hold down ‘ADVANCE’ push button for at least 2
seconds.
The “Test” LED will light and the Zone 1 Fault LED will
flash at a fast rate (faster than the fault warning flash
rate).
If you do not wish to test this zone then press ‘ADVANCE’
to move to the second zone.
To put the zone into “Test” press ‘SELECT / LAMP
TEST’.
If the zone is in “Test”, the LED is constant, and if it is to
be deselected then press ‘SELECT / LAMP TEST’ again.
Press ‘RESET’ button at any stage to accept settings and
revert to normal operating mode.
Disable Zone –
Repeat the above process until the “Test” LED goes out
and the “Disabled” LED illuminates.
Use the ‘ADVANCE’ and ‘SELECT / LAMP TEST’ keys
as previously described to select/deselect zones that are
to be disabled.
Press ‘RESET’ button at any stage to accept settings
and revert to normal operating mode.
Disable Sounders –
After progressing through all the Test & Disable zones
functions the “Sounder Fault / Disable” LED will
illuminate.
If the sounders are to be disabled/enabled use ‘SELECT /
LAMP TEST’ push button.
Press ‘RESET’ button at any stage to accept settings and
revert to normal operating mode or press ‘ADVANCE’
once more to exit the panel from this test/disable loop.
MAINTENANCE INFORMATION
All the components of this panel have been selected for the
intended purpose, and are expected to operate within their
specification when the environmental conditions outside the panel
comply with class 3k5 of IEC 721-3-3.
The battery has a manufacturers recommended life expectancy of
3-5 years.