List of warnings and errors
No. Name Warning
1
Error
1
Description
1 Safe * X Input Safe activated
2 Control signal X Value of control signal 3 mA (it applies to ranges 4 20/20 4 mA)
4 Torque X Induced torque beyond end-limit positions or disconnected torque sensor
6 Thermal protection X Thermal protection input activated
7 Sense of rotation X Reverse sense of rotation (for CONTROL only)
8 EEPROM X Wrong control sum of parameters in EEPROM
9 RAM X Wrong control sum of parameters in RAM
10 Parameters X Wrong parameters in EEPROM
11 Setting regimes X Setting regime from push-buttons or PC
12 Torque sensor X Disconnected or defective torque sensor
13 Sensor 1 X Error of sensor of position 1 (lowest stage)
14 Sensor 2 X Error of sensor of position 2
15 Sensor 3 X Error of sensor of position 3
16 Sensor 4 X Error of sensor of position 4 (highest stage)
17 Calibration X Autocalibration not carried out
18 Torque setting X Wrong setting of torques (parameters Torque O/Z 50/100 %)
19 Stroke X Wrong setting of stroke (parameters Position O/Z)
20 Rotation error X The actuator does not rotate
21 High temperature X Permitted max. temperature exceeded (parameter Temperature max.)
22 Low temperature X Permitted min. temperature exceeded (parameter Temperature min.)
23 LCD internal * X
Display of LCD internal does not communicate or not added
in parameter CAN of configuration
24 LCD external * X
Display of LCD external does not communicate or not added
in parameter CAN of configuration
25 Fieldbus * X
Module of industrial bus does not communicate or not added
in parameter CAN of configuration
26 CAN * X Error of bus CAN (short circuit, interruption, only sensor communicates)
27 Fieldbus activity* X Connection to industrial bus not active
28 Phase * X Inverse order of phases or some phase missing
29 Relay of service life X
Service life of relay MO/MZ at CONTROL exceeded
(parameter Relay of service life)
30 Reset X Non-standard Reset of unit induced (watchdog etc.)
31 ROM X Wrong control sum of program in ROM
32 CAN version * X
Sensor, LCD display or module Fieldbus have incompatible
versions of firmware
33 Wrong command * X Commands Open and Close entered at the same time
34 Wrong inertia - - Wrong inertia measured by autocalibration (for autocalibration only)
35 Wrong run-down - - Wrong run-down measured by autocalibration (for autocalibration only)
41 Wrong position X Servo-drive is in position 25 % behind working stroke
1
)
Assignment can vary depending on the version of firmware of the sensor control unit.
* Applies to DMS2 only.
Memory of number of induced warnings and errors
For all ascertained warnings and errors, DMS2.ED uses counters of occurrence of these warnings and errors during
operation of the system.
Values of the counters are stored to the EEPROM memory and are preserved even in case of the power supply fall-out.
Reading of the counters is possible by means of the program for PC
Clearing of the counters is possible by means of the program for PC with the level of authorization “SERVICE”.
Memory of recently induced warnings and errors
DMS2.ED stores three recently induced warnings and errors to the EEPROM memory.
Recent warnings and errors can be displayed and erased by means of the program for PC.