24
Tripping in end-limit positions
– Check and, if necessary, set the way of tripping in the end-limit positions::
– Torque
– Torque + position O
– Torque + position Z
– Torque + position O + Z
End-limit positions - working stroke
– Position Z
– Shift to position Closed either manually or by means of menu Motor in program DMS2.
–
The actuator can only be controlled by means of the program if no torque is induced. The torque should be left manually.
– Press push-button Z to confirm consent with the record.
– Position O
– Shift to position Open either manually or by means of menu Motor in program DMS2.
– The actuator can only be controlled by means of the program if no torque is induced. The torque should be left
manually.
– Press push-button O to confirm consent with the record.
Autocalibration
– The autocalibration can only be started by means of the program if no torque is induced. The torque should be left
manually.
– The autocalibration is started by push-button Start in program DMS2.
– Wait until the autocalibration is completed; information on its course is signalized next to push-button Start.
Other parameters
Check and, if necessary, change other parameters:
Control signal
4 – 20 mA 20 – 4mA 0 – 20 mA 20 – 0 mA
2 position Bus
Insensitivity 1 – 1 0 %
Function SAFE Open Close Stop To position
Active SAFE O V 230 V
Time of blocking torque
in end-limit positions
0 – 20 s
Position of blocking torque
in end-limit positions
1 – 10 %
Output of position signal 4 – 20 mA 20 – 4 mA
Function READY
Switched off Warning Errors Warning or error
- Combined error
Errors or not Errors or warning
Torque “O” or “Z”
remote or not remote
Switched off Position O Position Z
Torque O Torque Z
Torque and position O
Torque and position Z
Relay 1 – 4 Opening Closing Motion Position
position N Local control Emote control Control switched off
Torque O/Z Motion - blinker
Position Relay 1 – 4 0 – 100 %
Note: SAFE - input information on the error of an external device can be set so that the actuator would respond as to its own error.
Autodiagnostics
The table List of errors – same as for electronics DMS2 ED (page 14)
Memory of number of induced errors
– For all detected errors, DMS2 uses the counter of occurrence of these errors during operation of the system.
–
Values of the counters are stored to the EEPROM memory and are preserved even in case of the power supply fall-out.
– Reading and clearing of the counters is possible by means of the program for PC.