24
Tripping in end-limit positions
Check and, if necessary, set the way of tripping in the end-limit positions::
Torque
Torque + position O
Torque + position Z
Torque + position O + Z
End-limit positions - working stroke
Position Z
Shift to position Closed either manually or by means of menu Motor in program DMS2.
The actuator can only be controlled by means of the program if no torque is induced. The torque should be left manually.
Press push-button Z to confirm consent with the record.
Position O
Shift to position Open either manually or by means of menu Motor in program DMS2.
The actuator can only be controlled by means of the program if no torque is induced. The torque should be left
manually.
Press push-button O to confirm consent with the record.
Autocalibration
The autocalibration can only be started by means of the program if no torque is induced. The torque should be left
manually.
The autocalibration is started by push-button Start in program DMS2.
Wait until the autocalibration is completed; information on its course is signalized next to push-button Start.
Other parameters
Check and, if necessary, change other parameters:
Control signal
4 – 20 mA 20 – 4mA 0 – 20 mA 20 – 0 mA
2 position Bus
Insensitivity 1 – 1 0 %
Function SAFE Open Close Stop To position
Active SAFE O V 230 V
Time of blocking torque
in end-limit positions
0 – 20 s
Position of blocking torque
in end-limit positions
1 – 10 %
Output of position signal 4 20 mA 20 – 4 mA
Function READY
Switched off Warning Errors Warning or error
- Combined error
Errors or not Errors or warning
Torque “O” or “Z”
remote or not remote
Switched off Position O Position Z
Torque O Torque Z
Torque and position O
Torque and position Z
Relay 1 – 4 Opening Closing Motion Position
position N Local control Emote control Control switched off
Torque O/Z Motion - blinker
Position Relay 1 – 4 0 – 100 %
Note: SAFE - input information on the error of an external device can be set so that the actuator would respond as to its own error.
Autodiagnostics
The table List of errors – same as for electronics DMS2 ED (page 14)
Memory of number of induced errors
For all detected errors, DMS2 uses the counter of occurrence of these errors during operation of the system.
Values of the counters are stored to the EEPROM memory and are preserved even in case of the power supply fall-out.
Reading and clearing of the counters is possible by means of the program for PC.