13
EN
14
Battery
undervoltage
alarm point
[14] 44V Default
Battery undervoltage alarm point. When the battery
voltage is lower than the judgment point, an alarm
will be reported (the output will not be turned off).
The setting range is 40V~52V, the step is 0.4V. Valid
only when the battery type is custom and it is a lithium
battery
15
Battery Discharge
Limit Voltage
[15] 40V Default
The battery discharge limit voltage. When the battery
voltage is lower than the judgment point, the output
will be turned off immediately. The setting range is
40V~52V, the step is 0.4V. Valid only when the battery
type is custom and it is a lithium battery
16 Balanced charge [16] ENA Default
Turn on equalization charging. Valid only for open
lead-acid and sealed lead-acid batteries
17
Balanced charging
voltage
[17] 58.4V Default
Balanced charging voltage. The setting range is
48V~58.4V, the step is 0.4V. Valid only for open lead-
acid and sealed lead-acid batteries
18
Equalization
charging time
[18] 120 Default
Equalization charging time. The setting range is
5min~900min, the step is 5 minutes. Valid only for
open lead-acid and sealed lead-acid batteries
19
Equalization
charge delay
[19] 120 Default
Balanced charging delay. Setting range 5min~900min,
the step is 5 minutes. Valid only for open lead-acid
and sealed lead-acid batteries
20
Equalization
charge derating
time
[20] 30 Default
Equalization charge derating time. Setting range is
0~30 days, the step is 1 day. Valid only for open lead-
acid and sealed lead-acid batteries
21
Turn on
equalization
charging
[21] DIS Default Stop equalizing charging immediately
22
Energy saving
mode
[22] DIS Default Disable energy saving mode
23
Overload restarts
automatically
[23] ENA Default
Overload automatic restart. If the output is turned off
due to overload, the machine will restart the output
after 3 minutes delay. After 5 restarts in a row it will not
restart anymore.