EN
24
Over temperature
automatic restart
[24] ENA Default
Over-temperature automatic restart. If the over-
temperature occurs, the output will be turned off and
will be restarted when the temperature drops
25 Buzzer alarm [25] ENA Default Turn on the alarm
26
Mode switch
reminder
[26] ENA Default
When the status of the main input source changes, an
alarm will be triggered
27
Inverter overload
transfer to bypass
[27] ENA Default
When the inverter is overloaded, it will automatically
switch to the mains
28
Mains charging
current
[28] 230V/50A,
120V/30A Default
AC input current. Setting range 0~50A (for 230V);
0~30A (for 120V)
29
Output phase
adjustment
function
[29] DIS Default Output phase adjustment function
30
R485 address
setting
[30] 1 Default RS485 communication address. Setting range 1~254
35
Battery
Undervoltage
recovery point
[35] 50.4V Default
When the battery voltage is low, it must be higher than
this setting value to restore the battery inverter output
power. Setting range: 44V~58.4V
37
Full battery
recharge recovery
point
[37] 52V Default
When the battery is fully charged, the inverter stops
charging. When the battery voltage is lower than this
voltage value, charging will be resumed
38
AC output voltage
setting
[38] 230V Default
AC output voltage. Can be set to:
200/208/220/230/240V