EasyManua.ls Logo

AAF UV05 - UVC Configuration Parameters; UVC Configuration Parameters List

Default Icon
50 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
McQuay OM 751 47
UVC Configuration Parameters
UVC Configuration Parameters
The UVC is been provided with a number of configuration variables as listed in the following
table. These configuration variables are stored in UVC non-volatile memory. For a description
of supported network variables for each protocol, refer to Protocol Data Packet bulletin ED
15065.
Table 26: UVC configuration parameters (OM 751)
Configuration Parameter Name Abr. Notes Default
LUI Menu
Item
1
Occupied Cooling Setpoint
OCS 73°F (23°C)
Co
Standby Cooling Setpoint
SCS 77°F (25°C)
C5
Unoccupied Cooling Setpoint
UCS 82°F (28°C)
CU
Occupied Heating Setpoint
OHS 70°F (21°C)
Ho
Standby Heating Setpoint
SHS 66°F (19°C)
H5
Unoccupied Heating Setpoint
UHS 61°F (16°C)
HU
Local Bypass Time Tenant override
120 min
Space CO
2
Setpoint
2
CO
2
S 1200 PPM
Space Humidity Setpoint
2
RHS
used with both active (reheat) and passive dehumidification
sequences
60% Rh
Emergency Heat Enable 0 = disable, 1 = enable (uses auxiliary heat where primary heat is
not applicable)
1
H1
Emergency Heat Setpoint
EHS 54°F (12°C)
H2
Emergency Heat Shutdown
Configuration
0 = no emergency heat during shutdown, 1 = emergency heat
available during shutdown
0
H3
Wall Sensor Type
2
0 = +/- 3°F, 1 = 55°F to 85°F
0
r5
Slave Type Configuration
2
0 = independent slave, 1 = dependent slave
0
SL
OAD Min Position High-Speed Setpoint
OADH
(this variable will be factory set to 5% open when the unit is ordered
with optional CO
2
DCV)
20% open
o2
OAD Min Position Med-Speed Setpoint
OADM
(this variable is ignored when the unit is ordered with optional CO
2
DCV)
25% open
o3
OAD Min Position Low-Speed Setpoint
OADL
(this variable is ignored when the unit is ordered with optional CO
2
DCV)
30% open
o4
Exhaust Interlock OAD Min Position
Setpoint
EOAD
OA damper minimum position when the exhaust interlock input is
energized
99% open
o5
Energize Exhaust Fan OAD Setpoint
OADE
defines position above which exhaust fan output will be energized
12% open
o6
OAD Max Position Setpoint
OAMX 99% open
o7
OAD Lockout Enable 0 = disable, 1 = enable (this variable will be factory set to 1 when
the unit is ordered as a recirc unit with no OAD)
0
o8
OAD Lockout Setpoint
OALS
OA temperature below which the OA damper will remain closed
(this variable will be factory set to –99°C when the unit is ordered
as a recirc unit with no OAD)
36°F (2°C)
o9
Economizer Enable 0 = disable, 1 = enable
1
E1
Economizer OA Temp Setpoint
ETS 68°F (20°C)
E2
Economizer IA/OA Temp Differential
ETD 2°F (1°C)
e3
Economizer OA Enthalpy Setpoint
EES 25 btu/lb (58 kJ/kg)
e5
Economizer IA/OA Enthalpy Differential
EED 1.3 btu/lb (3 kJ/kg)
e6
External BI-3 Configuration 0 = Ventilation Lockout, 1 = Exhaust Interlock
0
B3
External BO-3 Configuration 0 = Exhaust Fan On/Off, 1 = Auxiliary Heat
0
B6
Filter Alarm Enable 0 = disable, 1 = enable
0
CE
Filter Change Hours Setpoint fan run hours between filter change alarms
700 hrs

Table of Contents