EasyManua.ls Logo

ABB 511 Series - Page 2

ABB 511 Series
23 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
IB
-
7.2
.
1.7
-
1
PAGE
2
SOLID
-
STATE
OVERCURRENT
RELAYS
INSTRUCTIONS
FOR
CIRCUIT
-
SHIELD
®
SOLID
-
STATE
RELAYS
DRAWOUT
SEMI
-
FLUSH
MOUNTED
SINGLE
PHASE
,
TWO
PHASE
,
AND
THREE
PHASE
TABLE
OF
CONTENTS
3
.
Be
sure
the
trip
circuit
is
interrupted
by
an
"
a
"
contact
to
remove
high
currents
from
solid
-
state
output
circuits
.
Solid
-
state
output
circuits
have
inherently
high
momentary
current
ratings
and
low
continuous
current
ratings
.
Never
exceed
the
ratings
.
4
.
When
applying
input
current
to
protective
relays
,
be
sure
to
interrupt
the
input
current
immediately
after
the
relay
operates
.
5
.
Load
(
trip
coils
or
auxiliary
relays
)
must
draw
at
least
0.10
amps
to
insure
operation
.
SCR
'
s
require
a
minimum
current
to
remain
conducting
after
triggering
.
Parallel
a
resistance
with
a
low
current
coil
to
guarantee
the
holding
current
,
if
necessary
.
6
.
Do
not
attempt
to
manually
operate
target
vanes
on
CIRCUIT
-
SHIELD
overcurrent
relays
.
Although
the
targets
return
their
indication
under
shock
,
they
can
be
damaged
by
manual
operation
with
a
pencil
or
pointed
object
.
7
.
Do
not
apply
high
voltage
tests
to
solid
-
staie
relays
.
If
a
control
wiring
insulation
test
is
required
,
bond
all
terminals
together
and
disconnect
ground
wire
before
applying
test
voltage
.
8
.
Besuretonotetheconnectionstoterminals
9
,
10
,
and
11
(
described
under
CONNECTIONS
on
page
3
)
required
for
the
proper
operation
of
the
TIME
and
INSTANTANEOUS
elements
.
Jumper
links
are
supplied
with
all
relays
.
9
.
Only
the
lower
circuit
ooard
of
the
CIRCUIT
-
SHIELD
overcurrent
relay
is
removable
.
This
board
should
insert
smoothly
.
Do
not
use
force
.
10
.
Note
that
removal
of
the
tap
block
pin
is
equivalent
to
setting
the
highest
tap
.
11
.
Follow
test
instructions
to
verify
that
the
relay
is
in
proper
working
order
.
CAUTtON
:
Since
troubleshooting
entails
working
with
energized
equipment
,
caution
should
be
taken
to
avoid
personal
shock
.
Only
competent
technicians
familiar
with
good
safety
practices
should
service
these
devices
.
Introduction
Precautions
Placing
Relay
into
Service
Testing
While
in
Service
Application
Data
Calibration
and
Acceptance
Testing
Pg
.
2
Pg
.
2
Pg
.
3
Pg
.
3
Pg
.
4
Pg
18
INTRODUCTION
These
instructions
contain
the
information
required
to
properly
install
,
operate
,
and
test
the
complete
line
of
Type
51
solid
-
state
overcurrent
relays
.
The
CIRCUIT
-
SHIELD
overcurrent
relay
is
housed
in
a
semi
-
flush
drawout
relay
suitable
for
conventional
panel
mounting
.
All
connections
to
the
relay
are
made
at
terminals
located
on
the
rear
of
the
case
and
clearly
numbered
,
one
(
1
)
through
twelve
(
12
)
.
CURRENT
,
TIME
,
and
INST
,
pickup
controls
are
lo
-
cated
on
the
front
panel
behind
a
removable
clear
plastic
cover
.
TIME
and
INST
,
target
indicators
are
also
mounted
on
the
front
panel
.
Both
targets
are
reset
by
means
of
a
pushbutton
extending
through
the
relay
cover
.
PRECAUTIONS
The
following
precautions
should
be
taken
when
applying
solid
-
state
relays
:
1
.
Incorrect
wiring
may
result
in
damage
to
solid
-
state
relays
,
Be
sure
wiring
agrees
with
the
connection
diagram
for
the
particular
relay
before
the
relay
is
energized
.
Be
sure
control
power
is
applied
in
the
correct
polarity
before
applying
control
power
.
2
.
Apply
only
the
rated
control
voltage
marked
on
the
relay
front
panel
.
Unlike
conventional
relay
contacts
,
solid
-
state
outputs
are
rated
for
a
particular
control
voltage
.
If
rectified
AC
voltage
is
used
in
place
of
a
battery
,
proper
filtering
will
be
required
to
insure
SCR
"
Holding
Current
"
.
Courtesy of NationalSwitchgear.com

Related product manuals