OBJECT REQUEST (Slave will parse) RESPONSE (Slave will respond with)
30 0 Analog input — any
variation
1 (read)
22 (assign class)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
30 1 32–bit analog input 1 (read) 00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
129 (response) 00,01 (start-stop)
17, 28 (index)
30 2 16–bit analog input 1 (read) 00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
129 (response) 00,01 (start-stop)
17, 28 (index)
30 3 32–bit analog input
without flag
1 (read) 00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
129 (response) 00,01 (start-stop)
17, 28 (index)
30 4 16–bit analog input
without flag
1 (read) 00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
129 (response) 00,01 (start-stop)
17, 28 (index)
30 5 Short floating point 1 (read) 00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
129 (response) 00,01 (start-stop)
17, 28 (index)
30 6 Long floating point 1 (read) 00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
129 (response) 00,01 (start-stop)
17, 28 (index)
32 0 Analog change event
— any variation
1 (read) 06 (no range, or all)
07, 08 (limited qty)
32 1 32–bit analog change
event without time
1 (read) 06 (no range, or all)
07, 08 (limited qty)
129 (response)
130 (unsol. resp)
17, 28 (index)
32 2 16–bit analog change
event without time
1 (read) 06 (no range, or all)
07, 08 (limited qty)
129 (response)
130 (unsol. resp)
17, 28 (index)
32 3 32–bit analog change
event with time
1 (read) 06 (no range, or all)
07, 08 (limited qty)
129 (response)
130 (unsol. resp)
17, 28 (index)
32 4 16–bit analog change
event with time
1 (read) 06 (no range, or all)
07, 08 (limited qty)
129 (response)
130 (unsol. resp)
17, 28 (index)
32 5 Short floating point
analog change event
without time
1 (read) 06 (no range, or all)
07, 08 (limited qty)
129 (response)
130 (unsol. resp)
17, 28 (index)
32 6 Long floating point
analog change event
without time
1 (read) 06 (no range, or all)
07, 08 (limited qty)
129 (response)
130 (unsol. resp)
17, 28 (index)
32 7 Short floating point
analog change event
with time
1 (read) 06 (no range, or all)
07, 08 (limited qty)
129 (response)
130 (unsol. resp)
17, 28 (index)
32 8 Long floating point
analog change event
with time
1 (read) 06 (no range, or all)
07, 08 (limited qty)
129 (response)
130 (unsol. resp)
17, 28 (index)
50 0 Time and date
50 1 Time and date 1 (read) 07, (limited qty = 1) 129 (response) 07 (limited qty = 1)
2 (write) 07, (limited qty = 1)
Table continues on next page