EasyManua.ls Logo

ABB Ekip Touch - Page 23

ABB Ekip Touch
64 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
PROTECTION SETTINGS SETUP FOR EKIP TOUCH TRIP UNITS 23
Step 35. Change the Ground Fault Time Delay / Time t4 setting to the value in the coordination study.

minus iconplus iconthe value in the coordination study
Confirm


Ground Fault / G Protection
36

Related product manuals