Control functions
Table 115. Synchrocheck (SYNCRSYN)
Characteristic Value
Operation accuracy At the frequency f = f
n
Voltage: ±1.0% or ±0.002 × U
n
Frequency: ±10 mHz
Phase angle ±2°
Reset time <50 ms
Reset ratio Typically 0.96
Operate time accuracy +90ms/0 ms
Table 116. Tap changer control with voltage regulator (OLATCC)
Characteristic
Value
Operation accuracy
1)
At the frequency f = f
n
Differential voltage Ud:
±1.0% of the measured value or ±0.004 × U
n
(in measured voltages <2.0
× U
n
)
Operation value:
±1.0% of the U
d
or ±0.004 × U
n
for U
s
= 1.0 × U
n
Operate time accuracy in definite time mode
1)
±1.0% of the set value or 0.11 s
Operate time accuracy in inverse time mode
1)
±15.0% of the set value or 0.15 s
(at theoretical B in range of 1.1…5.0) Also note fixed minimum operate
time (IDMT) 1 s
Reset ratio for control operation Typically 0.80 (1.20)
Reset ratio for analog based blockings (except run back raise voltage
blocking)
Typically 0.96 (1.04)
1) Default setting values used