Table 30. Directional residual overcurrent protection, four steps EF4PTOC
Function Range or value Accuracy
Operate current, step 1-4 (1-2500)% of IBase ±1.0% of I
r
at I ≤ I
r
±1.0% of I at I > I
r
Reset ratio > 95% at (10-2500)% of IBase -
Relay characteristic angle
(RCA)
(-180 to 180) degrees ±2.0 degrees
Operate current for directional release (1–100)% of IBase For RCA ±60 degrees:
±2.5% of I
r
at I ≤ I
r
±2.5% of I at I > I
r
Independent time delay at 0 to 2 x I
set
, step
1-4
(0.000-60.000) s ±0.2% or ±35 ms whichever is greater
Minimum operate time for inverse curves,
step 1-4
(0.000 - 60.000) s ±0.2% or ±35 ms whichever is greater
Inverse time characteristics, see Table 119,
Table 120 and Table 121
16 curve types See Table 119, Table 120 and Table 121
Second harmonic blocking (5–100)% of fundamental ±2.0% of I
r
Minimum polarizing voltage (1–100)% of UBase ±0.5% of U
r
Minimum polarizing current (2-100)% of IBase ±1.0% of I
r
Real part of source Z used for current
polarization
(0.50-1000.00) W/phase
-
Imaginary part of source Z used for current
polarization
(0.50–3000.00) W/phase
-
Operate time, start non-directional at 0 to 2 x
I
set
Min. = 15 ms
Max. = 30 ms
-
Reset time, start non-directional at 2 x I
set
to
0
Min. = 15 ms
Max. = 30 ms
-
Operate time, start non-directional at 0 to 10
x I
set
Min. = 5 ms
Max. = 20 ms
-
Reset time, start non-directional at 10 x I
set
to
0
Min. = 20 ms
Max. = 35 ms
-
Critical impulse time 10 ms typically at 0 to 2 x I
set
-
Impulse margin time 15 ms typically -
1MRK 506 384-BEN A
Line distance protection REL650 2.2
Product version: 2.2.1
ABB 45