Table 31. Four step directional negative phase sequence overcurrent protection NS4PTOC
Function Range or value Accuracy
Operate current, step 1 - 4 (1-2500)% of
lBase
±1.0% of I
r
at I £ I
r
±1.0% of I at I > I
r
Reset ratio > 95% at (10-2500)% of
IBase
-
Independent time delay at 0 to 2 x I
set
,
step 1 - 4
(0.000-60.000) s ±0.2% or ±35 ms whichever is greater
Minimum operate time for inverse curves,
step 1 - 4
(0.000 - 60.000) s ±0.2% or ±35 ms whichever is greater
Inverse time characteristics, see table
119, table 120 and table 121
16 curve types See table 119, table 120 and table 121
Minimum operate current, step 1 - 4 (1.00 - 10000.00)% of
IBase
±1.0% of I
r
at I ≤ I
r
±1.0% of I at I > I
r
Relay characteristic angle (RCA) (-180 to 180) degrees
±2.0 degrees
Operate current for directional release (1–100)% of
IBase
For RCA ±60 degrees:
±2.5% of I
r
at I ≤ I
r
±2.5% of I at I > I
r
Minimum polarizing voltage (1–100)% of
UBase
±0.5% of U
r
Operate time, start non-directional at 0 to
2 x I
set
Min. = 15 ms
Max. = 30 ms
-
Reset time, start non-directional at 2 x I
set
to 0
Min. = 15 ms
Max. = 30 ms
-
Operate time, start non-directional at 0 to
10 x I
set
Min. = 5 ms
Max. = 20 ms
-
Reset time, start non-directional at 10 x
I
set
to 0
Min. = 20 ms
Max. = 35 ms
-
Critical impulse time 10 ms typically at 0 to 2 x I
set
-
Impulse margin time 15 ms typically -
Transient overreach <10% at τ = 100 ms -
1MRK 506 384-BEN A
Line distance protection REL650 2.2
Product version: 2.2.1