GUID-83B0F607-D898-403A-94FD-7FE8D45C73FF v7
Table 86. Insulation supervision for liquid medium function SSIML
Function Range or value Accuracy
Oil alarm level 1.00-100.00 ±10.0% of set value
Oil lockout level 1.00-100.00 ±10.0% of set value
Temperature alarm level -40.00-200.00 ±2.5% of set value
Temperature lockout level -40.00-200.00 ±2.5% of set value
Time delay for oil alarm (0.000-60.000) s ±0.2% or ±250ms whichever is greater
Reset time delay for oil alarm (0.000-60.000) s ±0.2% or ±250ms whichever is greater
Time delay for oil lockout (0.000-60.000) s ±0.2% or ±250ms whichever is greater
Time delay for temperature alarm (0.000-60.000) s ±0.2% or ±250ms whichever is greater
Reset time delay for temperature alarm (0.000-60.000) s ±0.2% or ±250ms whichever is greater
Time delay for temperature lockout (0.000-60.000) s ±0.2% or ±250ms whichever is greater
GUID-B6799420-D726-460E-B02F-C7D4F1937432 v8
Table 87. Circuit breaker condition monitoring SSCBR
Function Range or value Accuracy
Alarm level for open and close travel time (0 – 200) ms ±3 ms
Alarm level for number of operations (0 – 9999) -
Independent time delay for spring charging
time alarm
(0.00 – 60.00) s ±0.2% or ±30 ms whichever is greater
Independent time delay for gas pressure alarm (0.00 – 60.00) s ±0.2% or ±30 ms whichever is greater
Independent time delay for gas pressure
lockout
(0.00 – 60.00) s ±0.2% or ±30 ms whichever is greater
CB Contact Travel Time, opening and closing ±3 ms
Remaining Life of CB ±2 operations
Accumulated Energy ±1.0% or ±0.5 whichever is greater
M14987-1 v6
Table 88. Fault locator LMBRFLO
Function Value or range Accuracy
Reactive and resistive reach (0.001-1500.000) Ω/phase ±2.0% static accuracy
Conditions:
Voltage range: (0.1-1.1) x U
r
Current range: (0.5-30) x I
r
Phase selection According to input signals -
Maximum number of fault
locations
100 -
M12700-1 v4
Table 89. Event list
Function Value
Buffer capacity Maximum number of events in the list 1000
Resolution 1 ms
Accuracy Depending on time synchronizing
1MRK 506 384-BEN A
Line distance protection REL650 2.2
Product version: 2.2.1
ABB 67